Fujitsu AS*G09KXCA Series Service Instruction page 42

Split type room air conditioner wall mounted type inverter
Table of Contents

Advertisement

Trouble shooting 5
INDOOR UNIT Error Method:
Indoor Unit Model Information Error
EEPROM Access Abnormal
Detective Actuators:
Indoor unit Controller PCB
Forecast of Cause:
1. External cause
Check Point 1-1 : Reset Power Supply and operate
Does Error indication show again?
YES
YES
Check Point 2 :
Check Indoor unit electric components
Check all connectors.
(loose connector or incorrect wiring)
Check any shortage or corrosion on PCB.
Check Point 3 : Replace Controller PCB
Change Controller PCB.
Indicate or Display:
Indoor Unit :
Operation indicator : 3 time Flash
Timer indicator : 2 time Flash
Economy indicator: Continuous Flash
Error code: [ E: 32 ]
Detective details:
When power is on and there is some below case.
1. When model information of EEPROM is incorrect.
2. When the access to EEPROM failed.
2. Defective connection of electric components
3. Controller PCB failure
NO
Check Point 1-2 :
Check external cause such as noise
Check if the ground connection is proper.
Check if there is any equipment that causes harmonic wave
near the power cable (Neon light bulb or any electronic
equipment which causes harmonic wave).
Note : EEPROM
EEPROM(Electronically Erasable and
Programmable Read Only Memory) is a non-
volatile memory which keeps memorized
information even if power is turned off. It can
change the contents electronically.
To change the contents, it uses higher
voltage than normal, and it can not change a
partial contents. (Rewriting shall be done
upon erasing the all contents.)
There is a limit in a number of rewriting.
02-09

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ao*g12kxca seriesAs*g12kxca seriesAo*g09kxca series

Table of Contents