3.3.4 Group E: Function Control Parameters

E0: Set point and control parameters

Code
E0.00 First frequency setting source
E0.01 First run command source
E0.02 Second frequency setting source 0...21
E0.03 Second run command source
Frequency setting source
E0.04
combination
Digital setting frequency
E0.06
saving mode
E0.07 Digital setting frequency
E0.08 Maximum output frequency
E0.09 Output frequency high limit
E0.10 Output frequency low limit
E0.15 Low speed running mode
E0.16 Low speed frequency hysteresis
E0.17 Direction control
E0.18 Direction change dead time
Acceleration / deceleration
E0.25
curve mode
E0.26 Acceleration time
E0.27 Deceleration time
E0.28 S-curve starting phase factor
E0.29 S-curve stopping phase factor
E0.35 Start mode
E0.36 Start frequency
30/51
Name
0...21
0...2
0...2
0...2
0...3
0.00...[E0.09] Hz
50.00...400.00 Hz
[E0.10]...[E0.08] Hz
0.00...[E0.09] Hz
0: Run with 0.00 Hz
1: Run with low limit frequen-
cy
0.00...[E0.10] Hz
0: Forward / Reverse
1: Forward only
2: Reverse only
3: Swap default direction
0.0...60.0 s
0: Linear mode
1: S-curve
0.1...6,000.0 s
0.1...6,000.0 s
0.0...40.0 %
0.0...40.0 %
0: Start directly
1: DC-braking before start
2: Start with speed capture
3: Automatic start / stop ac-
cording to setting frequency
0.00...50.00 Hz
VFC 3610 / VFC 5610
Setting range
DOK-RCON04-VFC-X610***-QU06-EN-P
Default
Min.
Attri.
0
Stop
0
Stop
2
Stop
1
Stop
0
Stop
0
Stop
50.00
0.01
Run
50.00
0.01
Stop
50.00
0.01
Run
0.00
0.01
Run
0
Stop
0.00
0.01
Stop
0
Stop
1.0
0.1
Stop
0
Stop
5.0
0.1
Run
5.0
0.1
Run
20.0
0.1
Stop
20.0
0.1
Stop
0
Stop
0.05
0.01
Stop