Bosch Rexroth AG
Start-up

3.2.4 Control the Motor

Step
Operation
Rotate the potentiometer counterclockwise
1
(leftwards) to the greatest extent
2
Press <Run> button
Rotate the potentiometer clockwise (right-
wards) slowly and till 5.00 is displayed
Observe the running status:
3
If the motor runs in the correct direction
If the motor runs steadily
If there is any abnormal noise or problem
4
Rotate the potentiometer clockwise
5
Rotate the potentiometer counterclockwise
6
Press <Stop> button
7
Check parameters without load
8
Check parameters with load
Tab. 3-5: Motor controlling procedure
VFC x610 has no internal contactor, and will be energized once the power
supply is connected. When the Run button is pressed down (or "Control by
terminals" is activated), the frequency converter will generate output.
By default, VFC x610 is set as:
– The frequency converter is started or stopped by the operating panel con-
trol.
– The output frequency is set by the potentiometer on the operating panel.
After powering on, please confirm:
– The setting frequency is displayed (no error display)
– The monitoring parameter is consistent with the actual situation.
By default, the frequency converter displays Output frequency in run status
and Setting frequency in stop status as the monitoring parameters. You may
change them to other parameters as described in parameters U1.00 and
U1.10. The factory defaults are based on standard applications with standard
motors.
For a frequency converter with dust cover, it is recommended to in-
stall an LED panel to perform the above operations.
22/51
VFC 3610 / VFC 5610
Description
Output frequency setting is 0.00
Control command active, 0.00 is displayed
The motor starts to run
Recommended operation:
Stop the motor immediately by switching off
the power if any abnormality occurs
Restart commissioning only after error cau-
ses have been removed
The motor accelerates
The motor decelerates
Stop command active, the motor stops
Settings according to actual applications
Settings according to actual applications
DOK-RCON04-VFC-X610***-QU06-EN-P