3.2.5 Motor Parameters Auto-Tuning

For SVC control and applications with higher requirement to control accuracy in
V/f control, motor parameter auto-tuning is necessary. Two modes of auto-tuning
are available, static auto-tuning and rotational auto-tuning. The former mode is
mainly used for V/f control and the latter is used ONLY for SVC control.
Check and make sure the following points before auto-tuning:
The motor is in standstill and not at high temperature.
The power rating of the frequency converter is close to that of the motor.
Set C1.05...C1.10 based on motor nameplate data. If the power factor data is
unavailable on the nameplate, keep the default setting of C1.10.
Disconnect the load from the motor shaft for rotational auto-tuning.
Set auto-tuning mode and start motor parameter auto-tuning:
Set the following parameter according to the control mode of the frequency con-
verter and the application situation.
Code
Name
C1.01
Motor parameter tuning
0: Inactive. The auto-tuning function is by default inactive.
1: Static auto-tuning. This mode is suggested to be used for V/f control. It can
also be used for SVC control when the load cannot be disconnected.
2: Rotational auto-tuning (suggested to be used for SVC control)
Press the <Run> button on the operating panel to start auto-tuning. In the proc-
ess of auto-tuning, a status code 'tUnE' will be displayed on the operating panel.
When the auto-tuning process is complete, the status code disappears and the
settings of the following parameters will be obtained automatically:
Static auto-tuning
Tab. 3-6: Parameters obtained by auto-tuning
DOK-RCON04-VFC-X610***-QU06-EN-P
Setting range
0...2
Rotational auto-tuning
Bosch Rexroth AG
Default
0
Parameters obtained by auto-tuning
C1.12: Motor rated slip frequency
C1.20: Motor no-load current
C1.21: Stator resistance
C1.22: Rotor resistance
C1.23: Leakage inductance
C1.24: Mutual inductance
C3.05: Current loop proportional gain
C3.06: Current loop integral time
C3.00: Speed loop proportional gain
C3.01: Speed loop integral time
Start-up
Min.
Attri.
Stop
23/51