Classification; Outlets - REMEHA Gas 310 ECO PRO-285 Installation, User And Service Manual

Gas 310 eco pro series, gas 610 eco pro series
Table of Contents

Advertisement

Gas 310 ECO PRO - Gas 610 ECO PRO
Type
Execution
B23
Open flue
(1)
B23P
B33
Open flue
C33
Room sealed flue 4
C53
Room sealed flue 4
C63
Room sealed flue 4
Room sealed flue 4
(2)
C83
Room sealed flue 4
(3)
C93
(1) Including the pressure classification P1
(2) An under pressure of 4 mbar is possible
(3) Ask your supplier for minimum dimensions of duct or sleeve
160514 - 125467-05
4.6.1.
The table specifies this classification in detail according to [.
Description
Without fire-stop approval.
4
Exhaust of combustion gases above the roof.
4
Air in the installation room.
4
Without fire-stop approval.
4
Common exhaust of combustion gases above the roof.
4
Common exhaust of combustion gases mixed in the air, air in the installation room (special
4
construction).
Exhaust of combustion gases above the roof.
The opening for the air-supply inlet is located in the same pressure zone as the vent (For
4
example, a concentric passage to the roof).
Closed equipment.
Separate channelling for the air-supply.
4
Separate channelling for the combustion gases.
4
Air-supply inlet and flue gas outlet are located in different pressure zones.
4
The manufacturer delivers this type of equipment without a supply or exhaust system.
The equipment can be connected on a so-called semi-CLV system (with common combustion
gas exhaust).
Channel for the air-supply and exhaust fumes in a duct or surrounded by a sleeve:
Concentric.
-
Eccentric; Air supply from the shaft.
-
Exhaust of combustion gases above the roof.
-
The opening for the air-supply inlet is located in the same pressure zone as the vent.
-
4.6.2.
The boilers can be used in room-ventilated or room-sealed
operation. The air supply connection kit must be used for closed
configurations (This is available as an accessory).
When exhausting combustion gases of type C6, the material of the
exhaust must conform with Gastec QA and/or be provided with CE
marking.
The flue gas pipes must be calculated conforming to EN 13384 (parts
1 & 2).

Classification

Outlets

For open exhaust of combustion gases above the roof, the
vent must always be provided with a suitable stainless steel
wire grill.
4. Installation
31