7. Troubleshooting for Outdoor Unit
7.1
Anti-icing Function
A5
Remote
Controller
Display
Outdoor Unit LED
A
Display
Method of
During cooling operation, indoor unit icing is detected by checking the temperatures sensed by
the indoor heat exchanger thermistor and room temperature thermistor that are located in a
Malfunction
shut-down room.
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Service Diagnosis
j
i
h
i
i
1
2
3
4
In cooling operation, the both conditions (A) and (B) are met for 5 minutes.
(A) Room temperature – Indoor heat exchanger temperature ≥ 10°C
(B) Indoor heat exchanger temperature ≤ –1°C
If the error repeats 4 times, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Wrong wiring or piping
Defective electronic expansion valve
Short-circuited air
Defective indoor heat exchanger thermistor
Defective room temperature thermistor
h
5
Troubleshooting for Outdoor Unit