SiBE121021_C
3.2
SA Indoor Unit - FFQ, FCQ, FDBQ, FBQ, FHQ Series
3.2.1 Relations between Modes
BRC1D528, BRC7E530W/531W, BRC7F532F/533F, BRC7EA63W/66
The following modes can be selected by using the [Inspection / Test] button on the remote
controller.
Indoor unit settings can be made.
Filter cleaning sign time
Others
Following codes can be checked.
Error codes
Indoor model code
Service Diagnosis
Press the [Inspection / Test]
button for more than 4 seconds.
Field
setting
mode
Press the [Inspection / Test]
button for more than 4 seconds.
Press the [Inspection / Test]
button once.
Inspection
mode
Press the [Inspection / Test] button once.
Service
mode
Press the [Inspection / Test] button once.
Normal
mode
Press the [Inspection / Test] button once
or leave the remote controller untouched
for 30 minutes.
After 10 seconds
Trial
operation
mode
Service Check Function
Service data can be obtained.
Error code history
Temperature data of various sections
Service settings can be made.
Forced fan ON
Airflow rate setting
Thermostat is forcibly turned on.
(R11277)
299