Daikin Super Multi NX FFQ25B8V1B Service Manual page 315

E-series, f-series, g-series
Hide thumbs Also See for Super Multi NX FFQ25B8V1B:
Table of Contents

Advertisement

SiBE121021_C
3.2.4 BRC7E530W/531W, BRC7F532F/533F, BRC7EA63W/66
To find the error code, proceed as follows:
Service Diagnosis
Step
Action
1
Press the [Inspection / Test] button to enter the inspection mode. Then the figure "0"
blinks on the UNIT No. display.
2
Press the UP or DOWN button and change the UNIT No. until the receiver of the remote
controller starts to beep.
If you hear...
3 short beeps
1 short beep
1 continuous beep
Service Check Function
[Inspection / Test] button
(R14392)
UP button
DOWN button
(R14424)
Then...
Follow all steps below.
Follow steps 3 and 4. Continue the
operation in step 4 until you hear a
continuous beep. This continuous
beep indicates that the error code
is confirmed.
There is no abnormality.
303