8.12 Outdoor Fan System Check

Check No.19

8.13 Capacitor Voltage Check

Check No.21
Before this check, be sure to check the main circuit for short circuit.
With the circuit breaker still on, measure the voltage according to the drawing of the model in
question. Be careful never to touch any live parts.

8.14 Power Module Check

Check No.22
Note:
Check to make sure that the voltage between (+) and (–) of the diode bridge (DB1) is approx.
0 V before checking.
Negative (–) terminal of
tester (positive terminal
(+) for digital tester)
Positive (+) terminal of
tester (negative terminal
(–) for digital tester)
Resistance in OK
Resistance in NG
Service Diagnosis
Check the outdoor unit fan system.
Outdoor unit fan running?
YES
Outdoor unit fan
system
functioning.
Multimeter
(DC. voltage range)
Disconnect the compressor harness connector from the outdoor unit PCB. To disengage the
connector, press the protrusion on the connector.
Follow the procedure below to measure resistance between the terminals of the DB1 and
the terminals of the compressor with a multi-tester. Evaluate the measurement results for a
judgment.
NO
Fan motor lead wire
connector disconnected?
NO
Go to Check No. 15.
DB1 (+)
UVW
UVW
DB1 (+)
several kΩ ~ several MΩ
YES
Reconnect the connector.
(R7159)
(R12869)
DB1 (–)
UVW
DB1 (–)
0 Ω or ∞
Check
UVW
369