3.1.4.2
Type of upstream condition
Description
Compensation for upstream pipe geometry.
Setting
Default
Related
Path
3.1.4.3
Upstream distance
Description
The distance to the upstream flow disturbance. The distance is given in pipe diameters.
Used for clamp-on flow profile compensation.
Setting
Default
Related
Path
3.1.4.4
Type of downstream condition
Description
Compensation for downstream pipe geometry.
Setting
Default
Related
Path
3.1.4.5
Downstream distance
Description
The distance to the downstream flow disturbance. The distance is given in pipe diameters.
FST020 Function manual
Function Manual, 09/2017, A5E42949526-AA
Straight run; Single elbow; Double elbow (in-plane); Double elbow (out-of-plane); Reducer;
Expansion
Straight run
Setup → Sensor settings → Upstream and downstream conditions → Type of upstream
condition
0 to 40
0
Setup → Sensor settings → Upstream and downstream conditions → Upstream distance
Straight run; Single elbow; Double elbow (in-plane); Double elbow (out-of-plane); Reducer;
Expansion
Straight run
Setup → Sensor settings → Upstream and downstream conditions → Type of downstream
condition
Setup
3.1 Sensor settings
23