Technical Data - Vacon NX_ 0003 5 User Manual

Nx series; nxs series; nxp series;
Table of Contents

Advertisement

24 • vacon
4.4

Technical data

Mains
connection
Motor
connection
Control
characteristics
Ambient
conditions
4
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Input voltage U
in
Input frequency
Connection to mains
Starting delay
Output voltage
Continuous output
current
Starting current
Output frequency
Frequency resolution
Control method
Switching frequency
(see parameter 2.6.9)
Frequency reference
Analogue input
Panel reference
Field weakening point
Acceleration time
Deceleration time
Braking torque
Ambient operating
temperature
Storage temperature
Relative humidity
Air quality:
chemical vapours
-
mechanical
-
particles
Altitude
Vibration
EN50178/EN60068-2-6
208...240V; 380...500V; 525...690V; –15%...+10%
45...66 Hz
Once per minute or less
2 s (FR4 to FR8); 5 s (FR9)
0—U
in
I
: Ambient temperature max. +122°F (50°C),
H
overload 1.5 x I
(1 min./10 min.)
H
I
: Ambient temperature max. +104°F (+40°C),
L
overload 1.1 x I
(1 min./10 min.)
L
I
for 2 s every 20 s
S
0...320 Hz (standard); 7200 Hz (special software)
0.01 Hz (NXS); Application dependent (NXP)
Frequency control U/f
Open Loop Sensorless Vector Control
Closed Loop Vector Control (NXP only)
NXS2/NX_5:
Up to NX_0061: 1...16 kHz; Default: 10 kHz
NXS2:
NX_0075 and greater: 1...10 kHz; Def: 3.6 kHz
NX_5:
NX_0072 and greater: 1...6 kHz; Def: 3.6 kHz
NX_6:
1...6 kHz; Default: 1.5 kHz
Resolution 0.1% (10-bit), accuracy ±1%
Resolution 0.01 Hz
8...320 Hz
0.1...3000 sec
0.1...3000 sec
DC brake: 30% * T
(without brake option)
N
FR4-FR9:
I
: -14°F (–10°C) (no frost)...+122°F (50°C)
H
I
: -14°F (–10°C)...+104°F (40°C)
L
FR10-FR12 (NEMA1):
I
/I
: -14°F (–10°C)...+104°F (40°C) (except NX_0461 6,
H
L
NX_0590 6,
NXP0820 6 : -14°F (–10°C) (no frost)...+95°F (35°C))
FR10 (NEMA12):
I
/I
: -14°F (–10°C) (no frost)...+104°F (40°C)
H
L
(except NX_0520 5,
NX_0416 6: -14°F ( –10°C) (no frost)...+ 95°F (35°C))
–104°F...+158°F
0 to 95% RH, non-condensing, non-corrosive,
no dripping water
IEC 721-3-3, unit in operation, class 3C2
IEC 721-3-3, unit in operation, class 3S2
100% load capacity (no derating) up to 3281 ft
1-% derating for each 328 ft above 3281 ft.
Max. altitudes: NXS2: 9843 ft; NX_5 (380...400V): 9843 ft;
NX_5 (415...500): 6562 ft; NX_6: 6562 ft
5...150 Hz
Displacement amplitude 0.04 in (peak) at 5...15.8 Hz (FR4...9)
Max acceleration amplitude 1 G at 15.8...150 Hz (FR4...FR9)
Displacement amplitude 0.01 in (peak) at 5-31 Hz (FR10...12)
Max acceleration amplitude 0.25 G at 31...150 Hz (FR10...12)
TECHNICAL DATA