36 • vacon
5.2

Cooling

Enough free space shall be left around the AC drive to ensure sufficient air circulation, cooling as well as
maintenance. You will find the required dimensions for free space in the tables below.
If several units are mounted above each other the required free space equals C + D (see figure below).
Moreover, the outlet air used for cooling by the lower unit must be directed away from the air intake of the
upper unit.
The amount of cooling air required is indicated below. Also make sure that the temperature of the cooling
air does not exceed the maximum ambient temperature of the converter.
5.2.1

FR4 to FR9

Type
0004—0012 NXS2
0.79
0003—0012 NX_5
0017—0031 NXS2
0.79
0016—0031 NX_5
0048—0061 NXS2
0038—0061 NX_5
1.18
0004—0034 NX_6
0075—0114 NXS2
0072—0105 NX_5
3.15
0041—0052 NX_6
0140—0205 NXS2
0140—0205 NX_5
3.15
0062—0100 NX_6
0261—0300 NXS2
0261—0300 NX_5
1.97
0125—0208 NX_6
Table 5-10. Mounting space dimensions
A
= clearance around the freq. converter (see also A
A
= clearance needed on either side of the AC drive for fan
2
change (without disconneting the motor cables)
**
= min. clearance for fan change
B
= distance from one AC drive to another or distance to
cabinet wall
C
= free space above the AC drive
D
= free space underneath the AC drive
5
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Dimensions [inch]
A
A
B
C
2
0.79
3.94
0.79
4.72
0.79
6.3
3.15
11.81
5.91
3.15
11.81
3.15
15.75
D
1.97
2.36
3.15
3.94
A
A
2
7.87
9.84
(13.78**)
Figure 5-11. Installation space
and B)
2
INSTALLATION
C
B
A
A
2
D
NK5_2
B