CABLING AND CONNECTIONS
6.1.1.6

Cable and fuse sizes, NX_5, FR10 to FR12

The table below shows typical cable sizes and types that can be used with the converter. The final selection
should be made according to local regulations, cable installation conditions and cable specification.
Frame
Type
NX0385 5
FR10
NX0460 5
NX0520 5
NX0590 5
FR11
NX0650 5
NX0730 5
NX0820 5
FR12
NX0920 5
NX1030 5
Table 6-4. Cable and fuse sizes for Vacon NX_5 (FR10 to FR12)
1)
based on correction factor 0.7
6.1.1.7

Cable and fuse sizes, NX_6, FR10 to FR12

The table below shows typical cable sizes and types that can be used with the converter. The final selection
should be made according to local regulations, cable installation conditions and cable specification.
Frame
Type
NX0261 6
NX0325 6
FR10
NX0385 6
NX0416 6
NX0460 6
FR11
NX0502 6
NX0590 6
NX0650 6
FR12
NX0750 6
NX0820 6
Table 6-5. Cable and fuse sizes for Vacon NX_6 (FR10 to FR12)
1)
based on correction factor 0.7
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Mains and motor
I
Fuse I
L
n
[A]
[A]
Cu: 2*(3*120+70)
385
400 (3 pcs)
Al: 2*(3*185Al+57Cu)
Cu: 2*(3*150+70)
460
500 (3 pcs)
Al: 2*(3*240Al+72Cu)
Cu: 2*(3*185+95)
520
630 (3 pcs)
Al: 2*(3*300Al+88Cu)
Cu: 2*(3*240+120)
590
315 (6 pcs)
Al: 4*(3*120Al+41Cu)
650
400 (6 pcs)
Al: 4*(3*150Al+41Cu)
Cu: 4*(3*120+70)
730
400 (6 pcs)
Al: 4*(3*185Al+57Cu)
Cu: 4*(3*150+70)
820
500 (6 pcs)
Al: 4*(3*185Al+57Cu)
Cu: 4*(3*150 + 70)
920
500 (6 pcs)
Al: 4*(3*240Al+72Cu)
Cu: 4*(3*185+95)
1030
630 (6 pcs)
Al: 4*(3*300Al+88Cu)
Mains and motor
I
Fuse I
L
n
[A]
[A]
Cu: 3*185+95
261
315 (3 pcs)
Al: 2*(3*95Al+29Cu)
Cu: 2*(3*95+50)
325
400 (3 pcs)
Al: 2*(3*150Al+41Cu)
Cu: 2*(3*120+70)
385
400 (3 pcs)
Al: 2*(3*185Al+57Cu)
Cu: 2*(3*150+70)
416
500 (3 pcs)
Al: 2*(3*185Al+57Cu)
Cu: 2*(3*150+70)
460
500 (3 pcs)
Al: 2*(3*240Al+72Cu)
Cu: 2*(3*185+95)
502
630 (3 pcs)
Al: 2*(3*300Al+88 Cu)
Cu: 2*(3*240+120)
590
315 (6 pcs)
Al: 4*(3*120Al+41Cu)
Cu: 4*(3*95+50)
650
400 (6 pcs)
Al: 4*(3*150Al+41Cu)
Cu: 4*(3*120+70)
750
400 (6 pcs)
Al: 4*(3*150Al+41Cu)
Cu: 4*(3*150+70)
820
500 (6 pcs)
Al: 4*(3*185Al+57Cu)
No. of
cable
1)
[mm
2
]
supply
cables
Even/Odd
Even/Odd
Even/Odd
Even
Cu: 4*(3*95+50)
Even
Even
Even
Even
Even
No of
cable
1)
supply
[mm
2
]
cables
Even/Odd
Even/Odd
Even/Odd
Even/Odd
Even/Odd
Even/Odd
Even
Even
Even
Even
vacon • 47
No. of motor
cables
Even/Odd
Even/Odd
Even/Odd
Even/Odd
Even/Odd
Even/Odd
Even
Even
Even
No of
motor
cables
Even/Odd
Even/Odd
Even/Odd
Even/Odd
Even/Odd
Even/Odd
Even/Odd
Even
Even
Even
6

Hide quick links: