Technical Data; Ac Drive Power Ratings; Mains Voltage 3Ac 208-240 V - Vacon 20 X Installation, Technical And Maintenance Manual

Table of Contents

Advertisement

Technical data

7.
T
ECHNICAL DATA
7.1

AC drive power ratings

7.1.1

Mains voltage 3AC 208-240 V

Mains Voltage 3AC 208-240V, 50/60 Hz
Input
Converter
current
type
0004
4.3
0005
6.8
0007
8.4
0011
13.4
0012
14.2
0017
20.6
Table 24. Power ratings of
NOTE: The rated currents in given ambient temperatures (in Table 24) are achieved only when
the switching frequency is equal to or less than the factory default.
Service support: find your nearest Vacon service center at www.vacon.com
Loadability
Rated continuous
50% overload
[A]
current I N
[A]
3.7
4.8
7.0
11.0
12.5
17.5
VACON
Max current
current
I S
[A]
5.6
7.4
7.2
9.6
10.5
14.0
16.5
22.0
18.8
25.0
26.3
35.0
®
20 X, supply voltage 208-240V.
vacon • 60
Motor shaft power
230V
240V
[kW]
[HP]
0.75
1.0
1.1
1.5
1.5
2.0
2.2
3.0
3.0
4.0
4.0
5.0
7

Advertisement

Table of Contents