A. Back Panel
B. Expander Module Flat Cable
C. Connecting Devices
Pin #1 to #8 can be configured either as zone inputs or
as PGM outputs.
Notes for EXP-33 Expander module wiring:
∗
Wired zone
terminals can be connected to a normally closed contact of a detector, switch (for example a Tamper switch
of any device), or a pushbutton, via a 2.2 K
detectors with up to 10mA standby current drain as DA-5; PL-1; Next_PIR; Vi-Motion; Vi-Pet.
The Speech Box is a wired remote speaker and microphone device for indoor use. It provides two-way voice
communication between the user and the central station using the control panel.
Caution! Do not install or remove the EXP-33 expander module when the control panel is powered by AC power or
battery.
16
EXP-33 EXPANDER MODULE WIRING
Figure 3.7b – EXP-33 Expander Module Wiring
Ω
resistor. The 12V terminal can be used to supply 12V to low power
For wired zones, the control panel classifies the
events according to the resistance it measures as
shown in the table below.
E.O.L or Arming Key Resistance
Range
~0 kΩ - 1.76 kΩ
∼1.77 kΩ - 2.64 kΩ
∼2.65 kΩ - 3.52 kΩ
∼3.53 kΩ - 5.26 kΩ
∞
∼5.26 kΩ -
D-306917
PowerMaster-33 G2 Installer's Guide
Zone
Arming Key
Tamper/
Tamper
Short circuit
Normal
Normal
Tamper
Tamper
Alarm
Alarm
Tamper
Tamper