KEB COMBIVERT F6 Instruction Manual page 27

Housing u 55...90kw 230v 75...200kw 400v
Hide thumbs Also See for COMBIVERT F6:
Table of Contents

Advertisement

Unit size 22...24 default without GTR7
L1 L2 L3
Unit size 22...24 special version with GTR7
+PA -
L1
L2
L3
Table 2.6
permissible cross-section flexible with wire-end ferrule
mm²
No.
min
1
50
3
0.2
4
35
5
10 mm stay bolt for ring thimble
T1 T2
+
-
V
W
U
K1K2
T1
T2
PB
U V W
Permissible cable cross-sections and tightening torques of the terminals
AWG/MCM
max
min
150
1/0 AWG
4
24 AWG
95
2 AWG
Terminals 230 V Class
Name Function
L1, L2,
3-phase mains connection
L3
U, V, W Motor connection
DC link voltage
250...370 V DC (200V class)
+, -
Connection for braking module,
filter or DC link coupling
(unsuitable for DC supply)
T1, T2 Connection for temperature sensor
Connection for shielding / earthing
Terminal in accordance with table 2.6
Name Function
L1, L2,
3-phase mains connection
L3
U, V, W Motor connection
PA, PB Connection for braking resistor
DC link voltage
250...370 V DC (200V class)
+PA, –
Connection for braking module,
filter or DC link coupling
(unsuitable for DC supply)
T1, T2 Connection for temperature sensor
K1, K2 GTR7 monitoring (optional)
Connection for shielding / earthing
max
300 MCM
25...30
10 AWG
3/0 AWG
15...20
Terminal in acc. with table 2.6
Maximum tightening torque
Nm
0.6
25
No.
5
1
3
5
No.
1
4
3
5
lb inch
270
5.3
180
220
GB - 27