Terminals 400 V Class
Unit size 26, 27 advanced special version
L1
L2
L3
Housing size 23...27 DC versionSpecial
version
--
++
GB - 24
K1K2
T1
T2
+PA -
PB
U V W
K1K2
T1
T2
-
+PA
PB
U V W
Terminal in accordance with table 2.5
Name Function
L1, L2,
3-phase mains connection
L3
U, V, W Motor connection
PA, PB Connection for braking resistor
DC link voltage
420...746 V DC (400V class)
Connection for braking module,
+PA, –
filter
or DC link coupling
(unsuitable for DC supply)
T1, T2 Connection for temperature sensor
K1, K2 GTR7 monitoring (optional)
Connection for shielding / earthing
Terminal in accordance with table 2.5
Name Function
DC voltage input
++, --
420...746 V DC (400V class)
U, V, W Motor connection
PA, PB Connection for braking resistor
DC link voltage
420...746 V DC (400V class)
Connection for braking module,
+PA, –
filter
or DC link coupling
(unsuitable for DC supply)
T1, T2 Connection for temperature sensor
Connection for shielding / earthing
No.
1
4
3
5
No.
1
4
3
5