Annex

Annex B

B.1

Certification

B.1.1

CE Marking

CE marked drive converters and servo drives were developed and manufactured to comply
with the regulations of the Low-Voltage Directive 2006/95/EC.
The inverter or servo drive must not be started until it is determined that the installation com-
plies with the Machine directive (2006/42/EC) as well as the EMC-directive (2004/108/EC)
(note EN 60204).
Drive converters and servo drives meet the requirements of the Low-Voltage Directive 2006/95/
EC. The harmonized standards of the series EN 61800-5-1 in connection with EN 60439-1
and EN 60146 were used.
This is a product of limited availability in accordance with IEC 61800-3. This product may
cause radio interference in residential areas. In this case the operator may need to take cor-
responding measures.
B.1.2

UL Marking

To be conform according to UL for the use on the North American and Canadian Market the
following instructions must be observed (original text of the UL):
• Control Board Rating (max. 30Vdc, 1A)
• „Maximum Surrounding Air Temperature 45°C"
• Degree of Overload Protection provided internally by the Drive, in percent of full load
current.
• Motor protection by adjustement of inverter parameters. For adjustement see application
manual parameters Pn.14 and Pn.15.
• Wiring Terminals marked to indicate proper connections for the power supply, load and
control circuit.
• „Use 75°C Copper Conductors Only"
• Terminals - Torque Value for Field Wiring Terminals, the value to be according to the R/C
or Unlisted Terminal Block used.
• Ground Terminals - „Ground Stud and Nut shall be connected with UL Listed Ring Con-
nectors (ZMVV), rated suitable". The suitable Torque Value of the Nuts in Nm.
• „Devices are intended for use in pollution degree 2 environment" (or similar wording)
• "Integral solid state short circuit protection does not provide branch circuit protection.
Branch circuit protection must be provided in accordance with the Manufacturer Instruc-
tions, National Electrical Code and any additional local codes", or the equivalent".
GB - 40
Acceptance according to UL is marked at KEB inverters with the adjacent
logo on the type plate.