Mitsubishi MELSEC Q Series Programming Manual page 368

Common instruction 1/2
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

PLSY
6.8.8
Fixed cycle pulse output (PLSY)
PLSY
PLSY
Setting
Data
n1
n2
D
Function
(1) Outputs a pulse at a frequency designated by n1 the number of times designated by n2, to
the output module with the output signal (Y) designated by
(2) Frequencies between 1 to 100 Hz can be designated by n1.
If n1 is other than 1 to 100 Hz, the PLSY instruction will not be executed.
(3) The number of outputs that can be designated by n2 is between 0 to 65535 (0000
FFFF
If n2 is set to "0", pulses are continuously output.
(4) Only an output number corresponding to the output module can be designated for pulse
output at
(5) Pulse output commences with the command leading edge of the PLSY instruction.
Pulse output is suspended when the PLSY instruction command goes OFF.
6-166
Command
n1 : Frequency or the number of the device where frequency is stored (BIN 16 bits)
n2 : Outputs count or the number of the device where the outputs count is stored (BIN 16 bits)
: Number of the device to which pulses are output (bits)
D
Internal Devices
R, ZR
Bit
Word
*1
).
H
.
D
High
Basic
performance
PLSY
n1
J
\
U
\G
Bit
Word
––
.
D
Process
Redundant
Universal
LCPU
n2
D
Constants
Zn
Other
K, H
––
––
––
*1: Only output (Y) can be used.
to
H

Hide quick links: