Mitsubishi MELSEC Q Series Programming Manual page 785

Common instruction 1/2
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

(b) When the model name has not been written to the target module (example: QX40)
b15
○+0
D
○+1
D
○+2
D
Nine words are used.
○+3
D
○+4
D
○+5
D
○+6
D
○+7
D
○+8
D
○+9
D
The following table shows the examples of character strings stored in
Target module
Input module
Output module
I/O combined module
Intelligent function module
[Character string indicating module type]
• Input module: INPUT
• Output module: OUTPUT
• I/O combined module: MIXED
• Intelligent function module*1: INTELLIGENT
• 1: Includes the QI60 and GOT.
[Character string indicating the number of points]
• 16 points:_16
• 32 points:_32
• 48 points:_48
• 64 points:_64
• 128 points:_128
• 256 points:_256
• 512 points:_512
• 1024 points:_1024
to
b8 b7
to
b0
1
4A
(N)
49
(I)
H
H
55
(U)
50
(P)
H
H
5F
(_)
54
(T)
H
H
36
(6)
31
(1)
H
H
00
00
H
H
00
00
H
H
00
00
H
H
00
00
H
H
00
00
H
H
Stores 1.
Indicates that the character
string consists of module type and
the number of points is stored.
Stores the character string consists
of module type and the number of points.
(stored in ASC II).
Stores the remaining model name and
00
to the 12th to 17th devices and
H
the 18th device, respectively.
+1 to
D
Stored character string
INPUT_16
OUTPUT_32
MIXED_64
INTELLIGENT_128
1
2
3
4
6
+9..
D
6
7
8
7-411

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec l series