Error
Error Contents and Cause
Code
[REMOTE PASS. ERR.]
Any of the following modules is not mounted on the
slot specified for the head I/O number of the
remote password.
• Serial communication module of function
version B or later
• Ethernet module of function version B or later
• Modem interface module of function version B or
later
■Collateral information
• Common information:-
• Individual information:-
3401
■Diagnostic Timing
• At power-on/At reset/STOP→RUN
[REMOTE PASS. ERR.]
Serial communication module, modem interface
module or Ethernet module of function version B or
later controlled by another CPU was specified in a
multiple CPU system.
■Collateral information
• Common information:-
• Individual information:-
■Diagnostic Timing
• At power-on/At reset/STOP→RUN
*4
The parameter No. can be derived by "dividing the start I/O number of the intelligent function module set by GX
Configurator" by 10
*5
The diagnostic timing of CPU modules except for Universal QCPU and LCPU can be performed only when switching the
CPU module status from STOP to RUN.
*8
The function version is B or later.
*12
This applies when the first five digits of the serial number is "07032" or later.
*14
This applies when the first five digits of the serial number is "08102" or later.
*15
This applies when the first five digits of the serial number is "09102" or later.
*16
This applies when the first five digits of the serial number is "09082" or later.
*17
This applies when the first five digits of the serial number is "10042" or later.
*18
The Universal model QCPU except the Q00UJCPU.
*19
This applies to the Universal model QCPU except for the Q00UJCPU, Q00UCPU, and Q01UCPU.
*20
This applies to the Universal model QCPU except for the Q00UJCPU, Q00UCPU, Q01UCPU, and Q02UCPU.
Corrective Action
Mount the following modules according to the
position specified with the start I/O number of the
remote password.
• Serial communication module of function
version B or later
• Ethernet module of function version B or later
• Modem interface module of function version B
or later
• Change it for the Ethernet module of function
version B or later connected by the host CPU.
• Delete the remote password setting.
.
H
LED Status
Corresponding
CPU Status
CPU
Q00J/Q00/Q01
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
*8
Qn(H)
QnPH
*18
QnU
12-57
1
2
*8
3
12
6
6
7
8