Alarms Set Up Group; Table 4-5 Alarms Group Definitions - Honeywell UDC3300 Product Manual

Universal digital limit controller
Hide thumbs Also See for UDC3300:
Table of Contents

Advertisement

4.6

Alarms Set Up Group

Introduction
Alarms group
prompts
Table 4-5
Alarms Group Definitions
Lower Display
Prompt
A1S1 VAL
A1S2 VAL
A2S1 VAL
A2S2 VAL
A1S1TYPE
42
An alarm is an indication that an event that you have configured (for
example—Process Variable) has exceeded one or more alarm limits. There
are two alarms available. Each alarm has two setpoints. You can configure
each of these two setpoints to alarm on various controller parameters.
There are two alarm output selections, High and Low. You can configure
each setpoint to alarm either High or Low. These are called single alarms.
You can also configure the two setpoints to alarm on the same event and
to alarm both high and low. A single adjustable Hysteresis of 0.0% to
5.0% is configurable for the alarm setpoint.
Table 4-5 lists all the function prompts in the "ALARMS" Set Up group
and their definitions.
Upper Display
Range of Setting
or Selection
Value in Engineering Units
Value in Engineering Units
Value in Engineering Units
Value in Engineering Units
NONE
PV
DEV
SHED
UDC3300 Limit Controller Product Manual
Parameter
Definition
ALARM 1 SETPOINT 1 VALUE—This is the value at
which you want the alarm type chosen in Prompt
"A1S1TYPE" to actuate. The value depends on what the
setpoint has been configured to represent. NO setpoint is
required for Communications SHED.
ALARM 1 SETPOINT 2 VALUE—This is the value at
which you want the alarm type chosen in Prompt
"A1S2TYPE" to actuate.
The details are the same as "A1S1 VAL".
ALARM 2 SETPOINT 1 VALUE—This is the value at
which you want the alarm type chosen in Prompt
"A2S1TYPE" to actuate.
The details are the same as "A1S1 VAL".
ALARM 2 SETPOINT 2 VALUE—This is the value at
which you want the alarm type chosen in Prompt
"A2S2TYPE" to actuate.
The details are the same as "A1S1 VAL".
ALARM 1 SETPOINT 1 TYPE—Select what you want
Setpoint 1 of Alarm 1 to represent. It can represent the
Deviation or Input 1, and if you have a model with
communications, you can configure the controller to alarm
on SHED.
NO ALARM
INPUT 1
DEVIATION
SHED FROM COMMUNICATIONS
Continued on next page
1/01

Advertisement

Table of Contents
loading

Table of Contents