Table 6-2 Equipment Needed - Honeywell UDC3300 Product Manual

Universal digital limit controller
Hide thumbs Also See for UDC3300:
Table of Contents

Advertisement

6.3
Preliminary Information,
Equipment needed
60
Table 6-2 lists the equipment you will need to calibrate the specific types
of inputs that are listed in the table. You will need a screwdriver to
connect these devices to your controller.
Table 6-2
Equipment Needed
Type of Input
Thermocouple Inputs
(Ice Bath)
Thermocouple Inputs
(Precision Resistor)
RTD (Resistance Thermometer
Device)
Milliampere, Millivolt, Volts, and
Radiamatic
UDC3300 Limit Controller Product Manual
Continued
Equipment Needed
• A calibrating device with ±0.02% accuracy for use
as a signal source such as a millivolt source.
• Thermocouple extension wire that corresponds with
the type of thermocouple that will be used with the
controller input.
• Two insulated copper leads for connecting the
thermocouple extension wire from the ice baths to
the precision calibrator.
• Two containers of crushed ice.
• A calibrating device with ±0.02% accuracy for use
as a signal source such as a millivolt source.
• Two insulated copper leads for connecting the
calibrator to the controller.
• A precision 500 ohm resistor ±0.1% connected
across input #1 terminals 25 (R) and 27 (–).
• A decade box, with ±0.02% accuracy, capable of
providing stepped resistance values over a
minimum range of 0 to 1400 ohms with a resolution
of 0.1 ohm.
• Three insulated copper leads for connecting the
decade box to the controller.
• A calibrating device with ±0.02% accuracy for use
as a signal source.
• Two insulated copper leads for connecting the
calibrator to the controller.
• Place current source at zero before switching ON.
• Do not switch current sources OFF/ON while
connected to the UDC3300 input.