Honeywell UDC3300 Product Manual page 48

Universal digital limit controller
Hide thumbs Also See for UDC3300:
Table of Contents

Advertisement

4.4
Input 1 Parameters Set Up Group,
Input 1 group
prompts, continued
Table 4-3
Input 1 Group Definitions, Continued
Lower Display
Prompt
XMITTER
(not available for FM
models)
38
Upper Display
Range of Setting
or Selection
B TC
E TC H
E TC L
J TC H
J TC L
K TC H
K TC L
NNM H
NNM L
NM90 H
NM90 L
NIC TC
R TC
S TC
T TC H
T TC L
W TC H
W TC L
100 PT
100 LO
200 PT
500 PT
RAD RH
RAD RI
LINEAR
SQROOT
UDC3300 Limit Controller Product Manual
Continued
Parameter
Definition
TRANSMITTER CHARACTERIZATION—This selection
lets you instruct the controller to characterize a linear input
to represent a non-linear one.
NOTE: Prompt only appears when a linear actuation is
selected at prompt 'IN1 TYPE".
FOR EXAMPLE: If input 1 is a 4 to 20 mA signal, but the
signal represents a type "K" thermocouple; select "K TC
H" and the controller will characterize the 4 to 20 mA
signal so that it is treated as a type "K" thermocouple input
(high range).
B Type Thermocouple
E Type Thermocouple High
E Type Thermocouple Low
J Type Thermocouple High
J Type Thermocouple Low
K Type Thermocouple High
K Type Thermocouple Low
NNM NiNiMo Type Thermocouple High
NNM NiNiMo Type Thermocouple Low
NiMo-NiCo Type Thermocouple High
NiMo-NiCo Type Thermocouple Low
NIC Nicrosil Nisil Thermocouple
R Type Thermocouple
S Type Thermocouple
T Type Thermocouple High
T Type Thermocouple Low
W5W26 Type Thermocouple High
W5W26 Type Thermocouple Low
100 Ohm–RTD
100 Ohm RTD low
200 Ohm–RTD
500 Ohm–RTD
Radiamatic (Type RH)
Radiamatic (Type RI)
Linear Range
Extracts Square Root
Continued on next page
1/01

Advertisement

Table of Contents
loading

Table of Contents