2.5
Wiring Diagrams,
Output and alarm
wiring diagram
Figure 2-7
Output and Alarm Wiring
L1
L2/N
22
23
Non-Latching
24
25
26
Non-Latching
27
Electromechanical relays are rated at 5 Amps @ 120 Vac or 2.5 Amps at 240 Vac.
1
Customer should size fuses accordingly.
1/01
Continued
Figure 2-7 shows the Output and Alarm wiring connections for Limit
controllers.
1
N.C.
Output
Relay #1
2
Latching
N.O.
3
To terminal
4
Alarm
N.C.
Relay #2
5
N.O.
6
To terminal
7
Alarm
N.C.
Relay #1
8
N.O.
9
To terminal
UDC3300 Limit Controller Product Manual
Limit Relay Load
1 or 3
Alarm Relay #2 Load
4 or 6
Alarm Relay #1 Load
7 or 9
1
Load
Supply
Power
Load
Supply
Power
Load
Supply
Power