9.4

Recommended Wiring Practices

General rules
Wire bundling
98
• All wiring must conform to local codes and practices.
• Wires carrying similar types of signals (Table 9-1) may be bundled
together, but bundles with different types of signals must be kept
separated to prevent inductive or capacitive coupling.
Table 9-1 shows what wiring should be bundled together to prevent
inductive or capacitive coupling.
Table 9-1
External Wiring
Wire Function
No.
Type
HIGH VOLTAGE
1
Line Power
2
Earth Ground
3
Line Voltage
Digital I/O
ANALOG I/O
4
Process Variable
RTD
Thermocouple
dc Millivolts
5
Low level (<100V)
4-20 mA dc
1-5 Vdc
DIGITAL I/O
6
Low Voltage (<100V)
7
Computer Interface
UDC3300 Limit Controller Product Manual
Are Shielded
Twisted Wires
Bundle No.
Recommended?
1
2
YES
3
YES
Continued on next page
NO