Table 2-1 Operating Limits - Honeywell UDC3300 Product Manual

Universal digital limit controller
Hide thumbs Also See for UDC3300:
Table of Contents

Advertisement

2.1
Overview,
CE Conformity
special conditions
(Europe)
Operating limits
6
Continued
Shielded twisted pair cables are required for all Analog I/O, Process
Variable, RTD, Thermocouple, dc millivolt, low level signal, 4-20 mA,
Digital I/O, and computer interface circuits.
We recommend that you review and adhere to the operating limits listed in
Table 2-1 when you install your controller.
Table 2-1
Operating Limits
Condition
Ambient Temperature
Relative Humidity
Vibration
Frequency
Acceleration
Mechanical Shock
Acceleration
Duration
Power
90 to 264 Vac
24 Vac/dc
Power Consumption
Frequency
(For Vac)
UDC3300 Limit Controller Product Manual
Specifications
32 to 131°F (0 to 55°C)
5 to 90 % RH at 40°C (104°F)
0 to 200 Hz
0.6 g
5 g
30 ms
90 to 264 Vac
50/60 Hz
(CSA models rated to 250 V maximum)
20 to 27 Vac
50/60 Hz
20 to 27 Vdc
0 Hz
18 VA maximum (90 to 264 Vac)
12 VA maximum (24 Vac/dc)
48 to 52 Hz
58 to 62 Hz
1/01

Advertisement

Table of Contents
loading

Table of Contents