Dent ELITEpro XC Operator's Manual page 55

Table of Contents

Advertisement

Small
Mini
Split Core
5A/15A
20A
(high
accuracy)
50A
50A
100A
Current Ratings of CTs Available from DENT Instruments
All of the CTs in the table are available from DENT Instruments.
These are internally shunted CTs (333.3 mV output) which
make them safe to handle even when connected to an
energized wire. They are also case-insulated for 600V phase-to-
phase service. Do not use on services with higher voltages.
The following table is a list of the UL recognized (61010-1) CTs
that can be used to maintain the UL listing.
High
Performance
20A Mini
CT-HSC-020-U
CT-HSC-020-B
CAUTION: DO NOT USE UNSHUNTED CTs. ONLY USE SHUNTED CTS WITH 333 mVAC OUTPUT. ALL
DIAGRAMS IN THIS SECTION SHOW THE CT PHASING ARROW POINTING TOWARD THE LOAD.
DENT
Instruments
ELITEpro
Medium
Midi
Split Core
100A
100A
200A
200A
400A
600A
High
Performance
Performance
50A Mini
100A Midi
CT-HSC-050-U
CT-HMC-0100-U
CT-HSC-050-B
CT-HMC-0100-B
UL Recognized CTs
Large Split
Clamp-
Core
on
600A
150A
1000A
500A
1000A
D
Y
ID
OU
the leads for a RōCoil up to 100
feet and a split core up to 1000
feet without loss of accuracy,
provided that the new wire is of
the same size or larger than the
CT lead wire.
High
High
Performance
200A Midi
CT-HMC-0200-U
CT-HMC-0200-B
Best Practices
RōCoil
(Rogowski)
5,000A
RōCoil mV™ Various
sizes available.
Contact DENT
Instruments.
K
? You can extend
NOW
RōCoil
(Rogowski)
CT-RXX-1310-U
CT-RXX-A4-U
55

Advertisement

Table of Contents
loading

Table of Contents