1) Enter a descriptive name in the Name field to identify your logger (optional).
2) Choose which Power Channel (CT) will be used to generate pulses from the drop-down list.
NOTE: The Power Channel drop-down list displays any enabled channel, allowing users to choose which
one(s) to use as a source for the pulses.
For example, if the setup table is only configured to measure one power channel, no other options will
be available in the Power Channel drop-down list. If the setup table is configured to measure two power
channels, you may choose either "1" or "2" from the drop-down list.
Users may wish to measure different pulse output variables on each channel. The Power Channels for
Digital 1 and Digital 2 may both be set to "1," or set to "1" and "2" in order to measure the pulse outputs
of two Physical Power Channels, or both may be set to "2." This enables users to measure pulse outputs
with different data in the Value and Scale described in the following sections.
3) Select a parameter (kWh, kVARh, or kVAh) to be used as the source for pulses from the Value
drop-down list.
The ELITEpro SP is capable of measuring the pulse output for KWh, KVAh, or KVARh. Only one may be
measured at a time if a single digital output channel is turned on, but users have the option of
measuring two different values concurrently from the same Power Channel if both Digital 1 and Digital 2
are in use.
4) Enter a scale in the Scale field to assign a significance to the pulses.
For example, if 22 is entered in the Scale field and kWh is selected for the Value, then each pulse
generated by the meter is equal to 22 kWh on the selected Power Channel.
NOTE: The maximum output rate is five (5) pulses per second, or 5Hz, with a maximum current of 75mA
and 30V DC.