3) Enter the raw sensor output minimum/maximum values. This data is typically found on the data
plate or data sheet of the sensor. Typical values for voltage devices are 0-5, 1-5, 0-10, 0-15, 0-30 for
voltage devices and 0–20, 4-20 for current loop devices.
4) Enter the corresponding engineering value to the sensor range (i.e., psig), the units, and the
average, minimum, and/or maximum record.
5) Click Send Setup Table to Logger to load the configuration into the data logger.
Best practices are to confirm the operation of all sensors. Use Logger > Display Real Time Values > Show
as Text or click the Display Real Time Text Values speed button before commissioning the logger for
prolonged data logging projects.
D
Y
K
? To trouble shoot or calibrate a
ID
OU
NOW
current or voltage sensor it is convenient to set
the physical range fields to be equal to the
electrical output values. The Real Time Values
readings can then be compared directly with
voltage or current measurements taken from a
DVM. Offset or gain errors can be corrected by
adjusting the min value or span (max–min).
S
S
T
END A
ETUP
ABLE TO THE
When you've finished selecting the configuration options, the setup table needs to be sent to the
ELITEpro XC.
1) After connecting to the logger, click on one of the SEND
SETUP TABLE to Logger command buttons on the Setup
Table screen. Separate buttons are available at the top
and lower left of the Setup Table screen. Sending a new
setup table to the logger deletes any data still stored in the logger. ELOG 15 displays the following
dialog box to ensure desired data is not lost:
DENT
Instruments
ELITEpro
L
OGGER
Best Practices
50