Using ELOG to connect to the ELITEpro XC access point
a) Disconnect from the USB connection using Logger > Connection > Terminate Connection or by
using the
Disconnect speed button.
b) Click the
Ethernet or Wi-Fi Connection speed button on the toolbar.
c) In the Network Connect dialog box, enter the IP Address, the Port Number entered during
setup, and click OK.
You may now use all of the capabilities of ELOG with the logger.
Using a Web Browser to connect to the ELITEpro XC Built-in Web Server
The ELITEpro XC includes a primitive internal web server that allows external devices such as smart
phones, tablets, PCs, etc., to connect to the logger and replicate a limited set of ELOG functions, i.e.,
viewing Real-Time Values or reading data. An additional password is required to access the server.
a) Select Logger > Communication > Logger Web/Mobile App Login Password. The Web/Mobile
App Login Password dialog box displays.
b) Open a web browser on the device that will communicate with the ELITEpro.
c) In the Address box of the browser, enter the IP Address of the ELITEpro XC as previously
configured. For example: http://192.168.1.1.
NOTE: If you selected a port other than port 80, add a colon followed by the port number to the
end of the IP Address, for example: http://192.168.1.1:3001.
d) When the login page appears, enter the Web/Mobile App Login Password you set in the dialog
box in Step A above. (The default password is 1234.) Please note that this is the distinct
password used to connect to the wireless access point.
You can view real-time values, view or download logged data as an Excel CSV file, start/stop logging,
clear the logger memory, and view the logger properties. Other ELOG functions such as creating or