Connecting a Communication Cable...................... 18 Connecting via a RS-485 Adapter ........................18 Installing the RS-485 Adapter to a Computer ....................19 Connecting via an Ethernet Cable (PowerScout 3 Plus only) ................20 Powering the PowerScout™ Meter ......................22 PowerScout™ Single-Phase Connections ......................22 COM - Communications LED ........................23 PS3 Serial ................................23...
Page 4
Firmware ..............................49 ..........................50 PPENDICES Appendix A—PowerScout™ Meter Wiring Diagrams ................50 PowerScout 3 Plus Wiring Diagrams ........................51 PowerScout 24 Wiring Diagrams ........................55 Appendix B—Connecting to a Network ....................59 Communication Protocol ..........................59 Daisy Chain Layout for RS-485 Network ......................59 Networking Using the BACnet/Modbus Protocol ....................59...
It is typically used for quick in-and-out monitoring of electrical systems. Up to 127 PowerScout 3 Plus meters may be connected to a single BACnet client for monitoring and recording power usage at multiple locations within a single site. Up to 247 meters may be connected to Modbus.
PowerScout™ Meter Safety Summary and Specifications All items conform to the following: This general safety information is to be used by both PS3P the Logger operator and servicing personnel. DENT Instruments, Inc. assumes no liability for user’s PS3E failure to comply with these safety guidelines.
Page 8
Do not use other CTs. Only use shunted CTs with a 333mV maximum output only. Serious shock hazard and logger damage can occur if unshunted CTs are used. The UL listing covers the use of the following DENT Instruments CTs that are UL Recognized and have been evaluated to IEC 61010-1: CT-HSC-020-X (20A Mini), CT-HSC-050-X (50A Mini), CT-HMC-0100-X (100A Midi), and the CT-HMC-0200-X (200A Midi).
Cette information de sécurité est destinée à être qui suit: PS3P utilisée à la fois par l'opérateur de l'enregistreur et PS3E le personnel de service. DENT Instruments, Inc n'assume aucune responsabilité pour l'utilisateur PS24-D qui ne respecte pas les directives en matière de PS48-D Conforme à...
Page 10
N’utilisez pas d'autres TC. Utilisez seulement des TC shuntée avec une puissance maximale 333mV. Un sérieux risque de décharge électrique et des dommages à l'enregistreur peut se produire si des TC pas shuntée sont utilisés. Utiliser seulement les CTs des DENT Instruments suivants qui sont énumérés jusqu'au 600V/CATIII. CT-HSC-020-U,CT-HSC-050-U,CT-HMC-0100-U,CT-HMC-0200-U L'équipement protégé...
Communication Rate (baud) BACnet: 9600, 19200, 38400, 76,800 (Default) Data Bits Parity None, Even, Odd Stop Bit 2, 1 Modbus Protocol Data Formats -or- BACnet Master Slave / Token Passing (MS/TP) protocol PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Page 12
PowerScout 24: 369 g (13 ounces), exclusive of CTs; with enclosure 609.51 g (21.5 ounces) PowerScout 3 Plus: 21.8 x 5.8 x 4.0 cm (8.6” x 2.283” x 1.6”) Dimensions PowerScout 24: 25.5 x 16.5 x 3.2 cm (10.9” x 7.4” x 5.1”) ViewPoint™...
• To mount the PowerScout 3 Plus use the two tabs provided at both ends of the case. Securely mount the PowerScout near a dedicated circuit disconnect breaker. Mounting tab, located on each...
USB cable and by inserting each white ferrule into the appropriate opening on the PowerScout meter. The red wire inserts in (+), the black wire in (-) and the green wire in (S). PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Page 15
2) Insert the CT wires into the connector/s. See the following CT Type Wiring Connections table for the correct wiring configuration. CT Type Wiring Connections Split-Core *2 wire PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Page 16
Mark the breaker as the “disconnect” for the PowerScout. Refer to the wiring diagrams in the Appendix for specifics of the wiring connections. Follow local electrical codes during this installation. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
White Brown Split Core mV White Black Clamp On mV Black Table II-1: CT Polarity NOTE: The directionality for Rogowski CTs is the arrow points toward the load (e.g. motor). PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Communication between a PowerScout meter and a logger is established with a serial RS-485 adapter or an Ethernet connection. A serial connection (RS-485) is limited in speed while a parallel connection (Ethernet) is much faster. PowerScout meters are ordered from DENT Instruments based on the type of desired connection.
4) Select Install the software automatically and click Next. 5) Click Finish when the installation is complete. 6) Remove the CD from your computer. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
4) Enter the IP Address for the Ethernet connection of the meter or select one of the previously used addresses from the drop-down list. The Scan Network button scans the network for possible meters. The Logger Selection dialog box displays. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Page 21
ViewPoint displays the following message when the connection is successful. 5) Enter the Port connected to the PowerScout. A checkbox is available to make the port the default. Different networks may require different ports. See your network administrator. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
PowerScout element. When paired with the right voltage phase, each CT provides individual kW/kWh readings for that CT channel. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Communications failure, or talking with BACnet while PS24 is in Modbus mode. Flashing Red The meter is receiving communication on the bus for a meter at another address. Table II-3: PS24 COM LED Signals PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
0.55 and the corresponding LEDs will be red. The following table describes the PhaseChek error conditions and the appropriate correction. Patent No. 7,612,552. U.S. Patent and Trademark Office. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Switch CT 3 with CT 2. CT 1 and CT 3 are reversed. Switch the position of the CTs flashing red. Table II-4: PhaseChek LED Error Resolution PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
PowerScout Meter Diagrams OWER COUT Serial PowerScout 3 Plus Ethernet PowerScout 3 Plus PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Page 27
Digital Port Indicator LEDs Communication LED Terminal Block for Digital Terminal Block for RS-485 Port Connections Connection Ethernet Port Connection Figure II-3: PowerScout 3 Plus Layout—US voltage wire colors shown PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Voltage Current Figure II-4: Four-wire Wye Use a Service Type 0 (zero) value for BACnet Object 12080 or a 0 (zero) value for Modbus Register 44607 on this wire configuration. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Figure II-5: Three Phase, Four-Wire Wye Use a Service Type 0 (zero) value for BACnet Object 12080 or a 0 (zero) value for Modbus Register 44607 on this wire configuration. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Communication configuration must be set up in the ViewPoint software even if you use a separate logger to record data RS-485 vs. Ethernet The type of connection is part of the configuration set up in the ViewPoint software PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Setting the Network Address Switches There are two rotary network address switches on a serial PowerScout 3 Plus, labeled Upper and Lower. These two switches are used to select the BACnet/Modbus address the client uses to communicate with the PowerScout.
DDRESSING AN LEMENT The PowerScout 3 Plus has only one element, whereas the PowerScout 24 has eight. Modbus and BACnet each use different ways to designate an element on the PS24. In Modbus mode, the decimal network switches set the base address for metering element “A.”...
When the Ethernet connection is selected an IP address is required. The screen display changes based on your connection selection. The Communications screen displays the RS- 485 connection as the default when PowerScout 24 is the selected meter. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Page 36
Network button allows you to browse your network for existing IP addresses. The Setup button allows you to set up a new IP address. 4) Enter a number for the port. Select Default Port to make this port the default. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
The supported baud rates include 9600, 19200, 38400, 57600 (Modbus only), 76800, and 115200 (Modbus only). NOTE: The baud rate on the user interface (ViewPoint) must match the PowerScout™ setting. If these settings differ, the PowerScout™ cannot communicate. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
™ Using ViewPoint Software ViewPoint™ software is used to monitor diagnostics and configure registers with DENT Instruments PowerScout meters. All of DENT Instruments PowerScout meters use ViewPoint software to communicate with the meter. The screen display for each ViewPoint tab can be somewhat different based on the selected meter (PS3/PS24) and the communication protocol (BACnet/Modbus).
Modbus addresses range from 01 (hex 01) to 247 (hex F7) max. The 00 setting is used to default the PowerScout communications mode to Modbus, 9600 baud, 8 bits no parity, and 1 stop bit. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
4) Enter the IP Address for the Ethernet connection of the meter or select one of the previously used addresses from the drop-down list. The Scan Network button scans the network for possible meters. The Logger Selection dialog box displays. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Page 41
ViewPoint displays the following message when the connection is successful. 5) Enter the Port connected to the PowerScout. A checkbox is available to make the port the default. Different networks may require different ports. See your network administrator. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
PowerScout—change the switch settings. The selected Baud Rate does not match the PowerScout baud rate—change the baud rate. For more information, refer to the Appendix, Troubleshooting Communication Issues. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
PS3, as the PS24 only has one digital output while the PS3 has two. The PS24 also has eight separate setups displayed on the screen and Pulse Input Scaling. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
1) Select WYE or DELTA as the wiring connection. A WYE connection automatically displays all three CTs. Any changes made to CT1 also apply to CT2 and CT3. Wye Wiring Connection PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Page 45
You can also duplicate changes made to one element to another element. Click Copy within the Element that you want to duplicate. The Copy Elements dialog box displays: Select the element(s) to obtain the wiring duplication. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
This indicates the PowerScout setup is correct. It may also be useful to use a handheld amp meter to test the current and compare its readings to the values provided on the Real-Time Values screen. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
4) Click Write to change to the new value. 5) Click Clear Totals to clear accumulated data. ? Accumulated data is registers/objects with a time reference, such as time since reset, kWh, demands, etc. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
In ViewPoint, accumulating objects/registers can be reset using the Read/Set or Read/Write tab. Click Clear Totals at the bottom of the screen. See the tables in the Appendices for a list all of the objects/registers available on the PowerScout meters. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
115,200 bps as the baud rate when firmware is currently loaded in meter. If a downloading firmware updates. later version of firmware is available, download it from the DENT Instruments : There are no baud rate settings when website. connected via Ethernet.
REDOUBLEMENT DE PRUDENCE QUAND ON FAIT LA CONNEXION. LES TENSIONS DEPASSANT 600 VOLTS PEUVENT EXISTER SUR LA PLAQUETTE ET PEUVENT METTRE LA VIE EN DANGER. LE RISQUE DE BLESSURES GRAVES OU DE MORT NE DOIT PAS ETRE SOUS-ESTIME. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Voltage Current Figure A-1: Three-wire Delta Use a Service Type 0 (zero) value for BACnet Object 12080 or a 0 (zero) value for Modbus Register 44607 on this wire configuration. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Page 52
Current Figure A-2: Two-wire Single Phase Use a Service Type 0 (zero) value for BACnet Object 12080 or a 0 (zero) value for Modbus Register 44607 on this wire configuration. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Page 53
Current Figure A-3: Three-wire Single Phase Use a Service Type 0 (zero) value for BACnet Object 12080 or a 0 (zero) value for Modbus Register 44607 on this wire configuration. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Page 54
Figure A-4: 3-Phase, 4-Wire Delta Use a Service Type 0 (zero) value for BACnet Object 12080 or a 0 (zero) value for Modbus Register 44607 on this wire configuration. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Figure A-5: Three Phase, Three Wire Delta Use a Service Type 0 (zero) value for BACnet Object 12080 or a 0 (zero) value for Modbus Register 44607 on this wire configuration. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Page 56
Figure A-6: Three Phase, Four Wire Delta Use a Service Type 0 (zero) value for BACnet Object 12080 or a 0 (zero) value for Modbus Register 44607 on this wire configuration. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Page 57
Modbus Register 44607 on this wire configuration. For a Single Phase connection, use a Service Type 2 value for BACnet Object 12080 or a 2 value for Modbus Register 44607 on this wire configuration. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Page 58
Modbus Register 44607 on this wire configuration. For a Single Phase connection, use a Service Type 2 value for BACnet Object 12080 or a 2 value for Modbus Register 44607 on this wire configuration. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
The BACnet/Modbus network administrator must assign a unique network address to each PowerScout 3 Plus using the rotary switches SW1-SW2 and to each PowerScout 24 using the rotary switches SW1, SW2, and SW3.
Object Picker List. 4) In the New Value field, enter 375 to change to Modbus mode. 5) Click Write. The status should say “Writing Value…” Return to the Communications tab and connect. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Page 61
Green *Factory Default After powering up the PowerScout 3 Plus, you will have 10 seconds to make changes. However, every time a rotary switch is changed, the 10 second timer resets. After 10 seconds of no switch action, the settings take effect and the switches revert to the Modbus Address selector if in Modbus mode or MAC address if in BACnet mode.
X scalar value = actual value : The Or, another way to state this formula is: register value must actual value/scalar value = register value be less than 65,535. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Reviewing this example using the data scalar 3 value of .1 provides the following result: 1,440kW/.1 = 14,400 Since 14,400 is less than 65,535, using data scalar 3 is a good choice for this example. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Serial Number 10 bytes (ASCII Alpha-Numeric) 44207 4206 Serial 2 “ 44208 4207 Serial 3 “ 44209 4208 Serial 4 “ 44210 4209 Serial Number last 2 bytes “ 44511 4510 Hardware ID Hardware revisions. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
CT Type All Writes same type for all CTs: 1=MilliVolt, 2=Rogowski (PS3 Only) 44526 4525 Slave ID !1=DENT, 1=Veris; Sets SLAVE_ID to Veris or DENT 44599 4598 CT Phase Shift All CT Phase Shift X 100 +/- (PS3 only) Writes same value to Registers 50199, 50299, &...
Page 66
Select 1=mV or 2=Rogowski CT2s 50299 10298 CT2 Phase Shift Phase Shift X 100 +/- 50300 10299 CT3 Integer Integer part of CT3 50301 10300 CT3 Decimal Fractional part of NV_CT3 PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Page 68
0 = output LOW (closed) Port 1 output control when 45302 1 = output HIGH (open) [default] 5301 used as an on/off—open/closed (PS24 only) switch Register 45110 must = 0 to use PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
(ABS) value of ABS (kVAR L1) + ABS (kVAR L2) + ABS (kVAR L3) 44011 4010 kVAh System LSW System Total Apparent Energy LSW (kVAh) 44012 4011 kVAh System MSW System Total Apparent Energy MSW (kVAh) PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Page 72
4083 kVAR Demand System Max window elapses. After a power cycle or CPU reset the value is not reset but it does not update again until 1 demand window elapses. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
System Positive Displacement Power Factor (dPF); System Register is 100x actual value (If the System dPF (44014) is positive, this register will contain that value else it will be zero) PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
System Net Negative Reactive Energy MSW (kVARh, resettable) 47010 7009 Negative kVAR System System Net Instantaneous Negative Reactive Power (kVAR) (net sum of all individual kVARs, if sum is positive value=0) PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Page 78
Volts L3 to L1 “ 47022 7021 Measured Line Frequency Line frequency x 10 (e.g., 602 = 60.2 Hz). On startup, 20 point averaging array is filled with first frequency read. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Page 81
CAM until 1 demand window elapses. After a power cycle or CPU reset the value is not reset but it does not update again until 1 demand window elapses. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Number of registers to read – high order bits Number of registers to read – low order bits CRC low order bits CRC high order bits Table D-4: Format for Modbus Command 03 PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Page 83
125 inclusive. For example, the address sent in the command message for register 40025 is actually 0024 (0018 hexadecimal), and the address sent for register 44062 is actually 4061 (0FDD hexadecimal). PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Page 84
The response is from the PowerScout at address 37. One byte was written to at the requested register, 0000. The value written was 0000. The CRC value was 5C8C. An echo of the original command after the contents are written is a valid response. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Page 85
00hFFhDENT Instruments PowerScout 3, PS3912001, FW Rev 1.0, Scalar 3 00hFFh DENT Instruments PowerScout 24, PS24712001, FW Rev 1.5, Scalar 3 The 00h is used for version control and the FFh indicates the meter is active. The 00h and FFh are two bytes in front of the string that are not displayed on the RTU.
Writing 1234 to the present value will reset all the accumulator Measurements objects (kWh, kVAh, kVARh) 10190 Communications protocol Used to change between BACnet and Modbus communications protocols. 12003 CT3 Phase Shift CT3 phase shift (degrees) PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Page 87
Line frequency setting for metering. 50 = 50 Hz, 60 = 60 Hz 12130 CT Type All Writes same type for all CTs: 1=MilliVolt, 2=Rogowski (PS3 Only) 12131 CT1 Type 1=MilliVolt, 2=Rogowski 12132 CT2 Type 1=MilliVolt, 2=Rogowski 12133 CT3 Type 1=MilliVolt, 2=Rogowski PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
0 = No pulses, Port may be used as an on/off— open/closed switch 13100 Digital Port 1 Configuration 44001 = System kWh pulses (PS3 only) Turns pulses on/off 44008 = System kVARh pulses 44011 = System kVAh pulses PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Equals kWh System / (Time Since Reset /3600 seconds/Hr) (resettable) 1100 kW System Maximum System Highest Instantaneous Draw Since Reset (kW) 1130 kW System Minimum System Lowest Instantaneous Draw Since Reset (kW, resettable) PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Page 90
System Total Reactive Power (kVAR). Signed net value of (kVAR L1) + (kVAR L2) + (kVAR L3) 5030 kVAR L1 Individual Phase Reactive Energy LSW (kVARh) (Signed) 5060 kVAR L2 “ 5090 kVAR L3 “ PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Page 91
9030 Apparent PF System System Total Power Factor (PF) (Signed) 9060 Displacement PF L1 Individual Phase displacement Power Factor (PF) 9090 Displacement PF L2 “ 9120 Displacement PF L3 “ PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Pulse output is used to generate pulses for external devices such as data loggers that can accept pulses but do not have BACnet or Modbus capability. The PowerScout 3 Plus can generate pulses based on accumulated value(s) such as system kWh, system kVARh, and system kVAh. When a pulse is generated by the meter, the orange LEDs will briefly flash, otherwise they will remain dark.
Page 95
44011 = System kVAh pulses 0 = normally open (HIGH) 45211 5210 Port 2 pulse output relay type 1 = normally closed (LOW) Table F-3: PS3 Modbus Digital Port 2 Pulse Output PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Page 96
44011 = System kVAh pulses 0 = normally open (HIGH) 13160 Port 2 pulse output relay type 1 = normally closed (LOW) Table F-5: PS3 BACnet Digital Port 2 Pulse Output PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
LED is lit when the port contacts close due to an external device. Pulse Input Port Functions Pulse input is used to count, accumulate and scale pulses received from non-DENT external pulse- initiating meters such as gas, water, or other electrical meters.
NSTALLING IRMWARE PDATES FOR THE OWER COUT PowerScout firmware updates are available from DENT Instruments, typically contained in a zip file that ™ can be downloaded, unzipped and installed using ViewPoint . The PowerScout requires ViewPoint 3.1 or later. Check the DENT Instruments website for the latest version of...
Page 104
For example, if the PowerScout has 100A CTs connected to it, the system reactive power (kVAR) is calculated by: Read register 40004 Multiply the value returned from register 40004 by 0.004 PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Page 107
VERIS Float Demand System Minimum 40308 System Minimum Demand LSW VERIS Float Demand System Maximum 40309 System Maximum Demand MSW VERIS Float Demand System Maximum 40310 System Maximum Demand LSW PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Appendix I—Conversion Table ECIMAL TO EXADECIMAL ONVERSION ABLE ™ Decimal values are used for the PowerScout 24 addresses. The table below shows the corresponding hex values. Decimal Decimal Decimal Decimal Decimal Decimal PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
USB port or move the USB cable to another USB port. Firmware Update Fails When the firmware update fails, select a slower baud rate and retry the update. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Page 111
Verify that the dip switches on the back of the USB to RS-485 adapter are set to the following: Reboot the computer. Click Connect on the Communications tab to reestablish communications. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
How many PowerScout instruments can be connected together? Up to 127 PowerScout 3 Plus/24 meters can be connected together on a BACnet MS/TP network. Up to 247 PowerScout 3 Plus and 30 PowerScout 24 meters can be connected together on a Modbus network.
Page 113
How do I update the firmware in BACnet mode? Currently, the PowerScout meter must be in Modbus mode in order to use ViewPoint to update the firmware (either through the software switch or the rotary switches). PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
(Modbus mode only) Most Significant Word. Unit of data with the high-order bytes at the left. PowerMeterStore 1.877.766.5412 www. .com Shop for Dent products online at:...
Page 115
Pulse Input Used for counting, accumulating, and scaling pulses received from non-DENT external pulse initiating meters such as gas, water, or other electrical meters. Pulse Output Pulse output is used to generate pulses for external devices such as data loggers that can accept pulses but do not have Modbus capability.