2) Mark the dedicated circuit as the disconnect for the ELITEpro XC.
ELITE
XC C
PRO
ONNECTIONS
The ELITEpro XC has the following connections:
Four current transformers (CTs).
Four voltage wire leads for connecting to voltage sources (L1, L2, L3, and Neutral).
Four analog input channels can be individually used to record process or environmental correlation
studies with power.
Power In/Out for connecting a DENT-provided external power supply or for powering external
devices. Maintain polarity as marked on the case:
In: 6-10 Vdc, maximum input of 500 mA
Out: 6 Vdc output, up to 200 mA for powering other external devices
USB connector for high speed downloads, setup, and communication with a computer. The ELITEpro
XC is also powered from the USB connection. If a USB cable is to be used inside an electrical panel, it
must be rated to the appropriate voltage or wrapped in an appropriately rated insulating sleeve. The
DENT-supplied cable does not meet this requirement without an insulating sleeve.
Ethernet port for connecting the device to a network.
An external coax connector for a Wi-Fi antenna may
also be present.
DENT
Instruments
ELITEpro
Prepping & Using the ELITEpro
"Roll" the device, as seen below.
D
Y
K
? It is often easier to
ID
OU
NOW
connect the CTs and voltage leads
to the load to be monitored first.
Then simply plug the voltage leads
and CT connectors into the
ELITEpro XC before mounting.