Procon A1M Installation Manual page 88

Hide thumbs Also See for A1M:
Table of Contents

Advertisement

Discrete Input (Digital Input)
Register Name
Addr
Maintenance Sign
83
Filter Sign
84
Actual Ventilation Mode
85
Setpoint 0.5ºC Increments
86
Availability
Heat/Cool or Cool-Only
87
Auto Operation Mode Availability
88
Heat/Cool or Heat-Only
89
Energy Consumption Data
90
Available
Bypass Damper Available
91
Auto Ventilation Mode Available
92
Operation Mode of Temperature
93
Control Unit
Outdoor Temperature Sensor
94
Return Air Temperature Sensor
95
Modicon
Details
Address
- Pressing ON/OFF button starts normal operation.
- When pressing the Ventilation button the Lossnay
remains in bypass mode
0 = Inactive
10084
1 = Active
0 = Inactive
10085
1 = Active
0 = Lossnay ventilation
10086
1 = Bypass ventilation
0 = Not available
10087
1 = Available
0 = Heat and Cool
10088
1 = Cool only
0 = Not available
10089
1 = Available
0 = Heat and Cool
10090
1 = Heat only
0 = Not available
10091
1 = Available
0 = Not available
10092
1 = Available
0 = Not available
10093
1 = Available
0 = Not available (not connected)
10094
1 = Available (connected)
0 = Not equipped
10095
1 = Equipped
0 = Not equipped
10096
1 = Equipped
Applicable Unit Type
86