Discrete Input (Digital Input)
Register Name
Addr
Heat Pump Slave 5 ON/OFF
12
(address 6 for CAHV/CRHV)
Heat Pump Slave 6 ON/OFF
13
(address 7 for CAHV/CRHV)
Heat Pump Slave 7 ON/OFF
14
(address 8 for CAHV/CRHV)
Heat Pump Slave 8 ON/OFF
15
(address 9 for CAHV/CRHV)
Boiler ON/OFF
16
External Heater Operation 1
Booster Heater 1 ON/OFF
17
Booster Heater 2 ON/OFF
18
Booster Heater 2+ ON/OFF
19
Immersion Heater ON/OFF
20
Water Pump 1 ON/OFF
21
Water Pump 2 ON/OFF
22
Water Pump 3 ON/OFF
23
3-Way Valve ON/OFF
24
2-Way Valve 2 ON/OFF
25
Modicon
Details
Address
10013
0 = Stop, 1 = Run
10014
0 = Stop, 1 = Run
10015
0 = Stop, 1 = Run
10016
0 = Stop, 1 = Run
0 = Stop, 1 = Run
10017
0 = Stop, 1 = Run
10018
0 = Stop, 1 = Run
10019
0 = Stop, 1 = Run
10020
0 = Stop, 1 = Run
10021
0 = Stop, 1 = Run
10022
0 = Stop, 1 = Run
10023
0 = Stop, 1 = Run
10024
0 = Stop, 1 = Run
10025
0 = Stop, 1 = Run
10026
0 = Stop, 1 = Run
Applicable Unit Type