Input Register (Analogue Input)
Register Name
Addr
Return Temperature – Zone 2
(signed)
72
External Water Temperature 6
(signed)
Return Temperature – Zone 2
73
External Water Temperature 6
Boiler Flow Temperature
74
(signed)
Boiler Flow Temperature
75
Boiler Return Temperature
76
(signed)
Boiler Return Temperature
77
DIP Switch SW2
78
Heat Pump Run Time
79
(hours)
Heat Pump Run Time
80
(hours x100)
Heat Pump Refrigerant Address
81
1 Run Time (hours x100)
Heat Pump Refrigerant Address
82
2 Run Time (hours x100)
Modicon
Details
Address
Temperature value in ºC multiplied by 100.
(see note *)
30073
Temperature value in ºC multiplied by 100.
(see note **)
Temperature value in ºC multiplied by 100.
(see note **)
30074
Temperature value in ºC multiplied by 100.
(see note **)
Temperature value in ºC multiplied by 100.
30075
(see note *)
Temperature value in ºC multiplied by 100.
30076
(see note **)
Temperature value in ºC multiplied by 100.
30077
(see note *)
Temperature value in ºC multiplied by 100.
30078
(see note **)
Bit 0 = Switch 2-1 (0 = OFF, 1 = ON)
30079
...
Bit 9 = Switch 2-10 (0 = OFF, 1 = ON)
Value in hours
30080
0 = 0 Hours ... 99 = 99 Hours
Value in hours multiplied by 100
0 = 0 hours
30081
...
65535 = 6553500 hours
Value in hours multiplied by 100
0 = 0 hours
30082
...
65535 = 6553500 hours
Value in hours multiplied by 100
0 = 0 hours
30083
...
65535 = 6553500 hours
Applicable Unit Type