Input Register (Analogue Input)
Register Name
Addr
Last Measured DHW Energy
161
Consumption – Wh part
Last Measured Total Energy
162
Consumption – kWh
Energy Produced Measured
163
Date – Year
Energy Produced Measured
164
Date – Month
Energy Produced Measured
165
Date – Day
Last Measured Heating Energy
166
Produced – kWh part
Last Measured Heating Energy
167
Produced – Wh part
Last Measured Cooling Energy
168
Produced – kWh part
Last Measured Cooling Energy
169
Produced – Wh part
Last Measured DHW Energy
170
Produced – kWh part
Last Measured DHW Energy
171
Produced – Wh part
Last Measured Total Energy
172
Produced – kWh
Flow Rate
173
Modicon
Details
Address
Last measured DHW energy consumption – Wh
30162
part of the value.
0 = 0Wh ... 99 = 99Wh
Last measured total energy consumption in Kwh.
30163
0 = 0kWh ... 65535 = 65535kWh
30164
Date of last energy produced measurement – Year
Date of last energy produced measurement –
30165
Month
30166
Date of last energy produced measurement – Day
Last measured heating energy produced – kWh
30167
part of the value.
0 = 0kWh ... 65535 = 65535kWh
Last measured heating energy produced – Wh part
30168
of the value.
0 = 0Wh ... 99 = 99Wh
Last measured cooling energy produced – kWh part
30169
of the value.
0 = 0kWh ... 65535 = 65535kWh
Last measured cooling energy produced – Wh part
30170
of the value.
0 = 0Wh ... 99 = 99Wh
Last measured DHW energy produced – kWh part
30171
of the value.
0 = 0kWh ... 65535 = 65535kWh
Last measured DHW energy produced – Wh part of
30172
the value.
0 = 0Wh ... 99 = 99Wh
Last measured total energy produced in Kwh.
30173
0 = 0kWh ... 65535 = 65535kWh
Litres per minute
30174
0 = 0 l/min ... 255 = 255 l/min
Applicable Unit Type
67