Advertisement

Input Register (Analogue Input)
Register Name
Addr
Room Temperature – Zone 2
54
(signed)
Room Temperature – Zone 2
55
Refrigerant Liquid Temperature
56
(signed)
Refrigerant Liquid Temperature
57
Outdoor Ambient Temperature
58
(signed)
Outdoor Ambient Temperature
59
Flow Temperature (signed)
60
Water Outlet Temperature
(signed)
Flow Temperature
61
Water Outlet Temperature
Return Temperature (signed)
62
Water Inlet Temperature (signed)
Return Temperature
63
Water Inlet Temperature
Tank Water Temperature
64
(signed)
Modicon
Details
Address
Temperature value in ºC multiplied by 100.
30055
(see note *)
Temperature value in ºC multiplied by 100.
30056
(see note **)
Temperature value in ºC multiplied by 100.
30057
(see note *)
Temperature value in ºC multiplied by 100.
30058
(see note **)
Temperature value in ºC multiplied by 10.
30059
0xFE70 = -40.0ºC ... 0x036B = 87.5ºC
Temperature value in ºC multiplied by 10.
30060
0x0000 = 0.0ºC ... 0x036B = 87.5ºC.
Temperature value in ºC multiplied by 100.
(see note *)
30061
Temperature value in ºC multiplied by 100.
(see note *)
Temperature value in ºC multiplied by 100.
(see note **)
30062
Temperature value in ºC multiplied by 100.
(see note **)
Temperature value in ºC multiplied by 100.
(see note *)
30063
Temperature value in ºC multiplied by 100.
(see note *)
Temperature value in ºC multiplied by 100.
(see note **)
30064
Temperature value in ºC multiplied by 100.
(see note **)
Temperature value in ºC multiplied by 100.
30065
(see note *)
Applicable Unit Type
58

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melcobems mini