Procon A1M Installation Manual page 68

Hide thumbs Also See for A1M:
Table of Contents

Advertisement

Input Register (Analogue Input)
Register Name
Addr
Model Profile 1
151
Model Profile 2 (refrigerant
152
address)
Energy Consumption Measured
153
Date – Year
Energy Consumption Measured
154
Date – Month
Energy Consumption Measured
155
Date – Day
Last Measured Heating Energy
156
Consumption – kWh part
Last Measured Heating Energy
157
Consumption – Wh part
Last Measured Cooling Energy
158
Consumption – kWh part
Last Measured Cooling Energy
159
Consumption – Wh part
Last Measured DHW Energy
160
Consumption – kWh part
Modicon
Details
Address
0 = FTC2B
1 = FTC4
2 = FTC5
128 = CAHV1A
129 = CAHV1B
130 = CRHV1A
30152
131 = CRHV1B
132 = EAHV1A
133 = EAHV1B
134 = QAHV1A
135 = QAHV1B
144 = PWFY1
0 = Address 0
...
30153
255 = Address 255
(addresses 7 – 255 not used for FTC)
Date of last energy consumption measurement –
30154
Year
Date of last energy consumption measurement –
30155
Month
Date of last energy consumption measurement –
30156
Day
Last measured heating energy consumption – kWh
30157
part of the value.
0 = 0kWh ... 65535 = 65535kWh
Last measured heating energy consumption – Wh
30158
part of the value.
0 = 0Wh ... 99 = 99Wh
Last measured cooling energy consumption – kWh
30159
part of the value.
0 = 0kWh ... 65535 = 65535kWh
Last measured cooling energy consumption – Wh
30160
part of the value.
0 = 0Wh ... 99 = 99Wh
Last measured DHW energy consumption – kWh
30161
part of the value.
0 = 0kWh ... 65535 = 65535kWh
Applicable Unit Type
66

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melcobems mini