Initialisation - Procon A1M Installation Manual

Hide thumbs Also See for A1M:
Table of Contents

Advertisement

4.3. Initialisation

When the MelcoBEMS MINI (A1M) powers up it will set the mode, which will be determined by the room temperature.
If less than the Heating Setpoint the unit will be set to HEAT mode with a setpoint of 28ºC.
If greater than or equal to the Cooling Setpoint the unit will be set to COOL mode with a setpoint of 19ºC.
If between the Heating and Cooling Setpoints the unit will be set to FAN mode.
13

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melcobems mini

Table of Contents