MelCOMMS MINI
FOR INSTALLERS
INSTALLATION MANUAL
Manual version 1.0.0
Firmware version 1.0.0
For safe and correct use, please read this installation manual thoroughly before installing the PROCON
MelCOMMS MINI.

Advertisement

Table of Contents
loading

Summary of Contents for Procon MelCOMMS MINI

  • Page 1 Procon MelCOMMS MINI FOR INSTALLERS INSTALLATION MANUAL Manual version 1.0.0 Firmware version 1.0.0 For safe and correct use, please read this installation manual thoroughly before installing the PROCON MelCOMMS MINI.
  • Page 3: Preface

    The product has been designed to operate between -20° C and +60° C Shielded Signal Cables: Use only shielded cables for connecting peripherals to any Procon MelCOMMS MINI device to reduce the possibility of interference with radio communications services. Using shielded cables ensures that you maintain the appropriate EMC classification for the intended environment.
  • Page 4: Disclaimer

    Disclaimer Warranty: All products manufactured on behalf of Mitsubishi Electric UK are warranted against defective materials for a period of three years from the date of delivery to the original purchaser. Warning: Mitsubishi Electric UK assumes no liability for damages consequent to the user of this product. We reserve the right to change this manual at any time without notice.
  • Page 5: Amendment Register

    Amendment Register Latest Document Firmware Date Author Notes Version Version 1.0.0 1.0.0 12/07/17 Initial version. Any additional notes since printing will be appended to the rear of this document on separate sheets of paper. • iii •...
  • Page 6 [Fig. 1]...
  • Page 7 [Fig. 2] Wiring Diagram...
  • Page 8 [Fig. 3] MelcoBEMS MINI (A1M) MelcoBEMS MINI (A1M) RS-485 resistors DIP switch configuration LK1 = Line A pull-up resistor LK2 = A-B termination resistor Each MelcoBEMS MINI (A1M) unit must have a LK3 = Line B Pull-down resistor unique address on the RS-485 bus. The baud rate must be set to 9600.
  • Page 9: Table Of Contents

    Contents   Preface ..................................... i   Safety warnings ................................i   Disclaimer ..................................ii   Amendment Register ..............................iii     Safety precautions ..............................5     Connecting Mains Power ............................. 6     Overview ................................7     Getting Started ..............................8  ...
  • Page 10: Safety Precautions

    1. Safety precautions Before installing the unit, make sure you read all the “Safety precautions” The “Safety precautions” provide very important points regarding safety. Make sure you follow them Symbols used in the text Warning: Describes precautions that should be observed to prevent danger of injury or death to the user. Caution: Describes precautions that should be observed to prevent damage to the unit.
  • Page 11: Connecting Mains Power

    A 6A single gang fused switch must be provided in-line with the mains supply and be in close proximity to the MelCOMMS MINI enclosure. It must be clearly marked as the disconnecting device. The supply should also be fed via a 6amp type B circuit breaker in the distribution box.
  • Page 12: Overview

    Compatible Air-To-Air model numbers can be found in Appendix A of this document. Figure 1 shows the MelCOMMS MINI dimensions. Figure 2 shows the MelCOMMS MINI wiring diagram for connections to an external fault relay, high temperature alarm relay and multiple MelcoBEMS MINI (A1M) units.
  • Page 13: Getting Started

    4. Getting Started 4.1. Unpacking The MelCOMMS MINI is supplied with the following components: Procon MelCOMMS MINI unit. 2x Procon MelcoBEMS MINI (A1M) units. This installation instruction manual. Please contact your supplier if any of these components are missing. 4.2. Before switching ON...
  • Page 14: Installation

    5. Installation 5.1. Physical connection The MelCOMMS MINI has four screw holes on the base plate of the panel. These can be used to attach the unit in place. Please secure the MelCOMMS MINI before powering the unit on. 5.2. Power supply A double pole (Live and Neutral) 5A switch or circuit breaker must be provided in line with the supply to the MelCOMMS MINI power supply and be in close proximity to it.
  • Page 15: Configuration

    The configuration is done using the 12x DIP switches, 4x digital inputs and 4x configurable inputs (which are fixed as digital inputs). To help installers who are already familiar with the PANEL_RS product the 4x digital inputs on the MelCOMMS MINI will be used as follows:...
  • Page 16 DIP Switch Usage Number of units connected [1-1 | 1-2 | 1-3] Number of units running [1-4 | 1-5 | 1-6] Days between rotation [1-7 | 1-8] = 1 day = 3 days = 5 days = 7 days Temperature setpoint (ºC) [2-1 | 2-2 | 2-3] = 18ºC = 19ºC...
  • Page 17: Initial Power On

    A communication fault between MelCOMMS MINI and one or more MelcoBEMS MINI (A1M) units. A fault code read from any MelcoBEMS MINI (A1M) unit which is not 8000 (8000 = OK).
  • Page 18: Rs-485 Comms Status Led

    5.6.4. RS-485 Comms Status LED Next to the DIP switches are two LEDs, one of these will constantly be ON and the other will flash to indicate successful Modbus communication with the MelcoBEMS MINI (A1M) units. If both are permanently ON then this indicates no communication with the MelcoBEMS MINI (A1M) units.
  • Page 19: Control Functionality

    6. Control Functionality 6.1. Automatic Mode When the switch on the front panel is set to ‘Automatic’ the MelCOMMS MINI will perform Backup & Rotate functionality. 6.1.1. Backup & Rotate A common installation scenario is a number of split systems that operate on a cyclical basis, with one unit on backup to operate in case of failure.
  • Page 20: Manual Mode

    6.4. Modbus Slave Test Mode MelCOMMS MINI can be put into Modbus slave test mode by powering the unit up with the 8 DIP switches 1-1 to 1-8 all in the OFF position. In this mode the MelCOMMS MINI unit will not attempt to communicate with any MelcoBEMS MINI (A1M) devices, the RS-485 port will instead be used to provide Modbus RTU Slave functionality.
  • Page 21 Input Status Registers (Digital Inputs) Modicon Register Name Address Details Address Digital Input 1 state 10001 Digital Input 2 state 10002 Digital Input 3 state 10003 0 = Input open circuit (no wire link present) Digital Input 4 state 10004 1 = Input closed circuit (wire link present) Input IN01 state 10005...
  • Page 22: Troubleshooting

    7. Troubleshooting Problem Possible Cause Solution No power from fused spur. Check fused spur Unit does not power up, Check 230V mains voltage into power supply and Faulty power supply. power LED is OFF 24VDV output. Blown power supply fuse. Check fuse and replace if needed Fault code read from indoor unit Check indoor units for problems.
  • Page 23: Appendix A - Compatible Air-To-Air Units

    Appendix A – Compatible Air-To-Air units UK Models M Series MSZ-SF25/35/50VE MSZ-GF60/71VE MSZ-EF25/35/50VES/VEW/VEB MSZ-FH25/35VE MSZ-FD25/35VA MSZ-GE22/25/35/50/60/71VA MSZ-GC22/25/35VA MSZ-GB50VA MSZ-GA22/25/35/50/60/71VA MFZ-KA25/35/50VA Mr Slim PCA-RP50/60/71/100/125/140KAQ PEAD-RP35/50/60/71/100/125/140JAQ PEAD-RP35/50/60/71/100/125/140EA/EA2 PEA-RP200/250GAQ PKA-RP35/50HAL PKA-RP60/71/100KAL PLA-ZRP35/50/60/71/100/125/140BA/BA2 PLA-RP35/50/60/71/100/125/140BA/BA2/BA3 PLA-RP35/50/60/71/100/125/140AA/AA2 PSA-RP71/100/125/140KA PSA-RP71/100/125/140GA SEZ-KD25/35/50/60/71VAQ SEZ-KA35/50/60/71VA SLZ-KA25/35/50VAQ SLZ-KA25/35/50VA Models Not Supported: MSZ-HJ25/35VA MSZ-HC25/35VA/VAB PCA-RP71/125HA/HAQ...
  • Page 24 Please be sure to put the contact address/telephone number on this manual before handing it to the customer. MITSUBISHI ELECTRIC UK MITSUBISHI ELECTRIC UK, TRAVELLERS LANE, HATFIELD, HERTFORDSHIRE, AL10 8XB...