Holding Register (Analogue Output)
Register Name
Addr
Heat Source Status
80
[READ ONLY]
Temperature Setpoint – Zone 1
(signed)
81
[READ ONLY]
Temperature Setpoint – Zone 1
82
[READ ONLY]
Temperature Setpoint – Zone 2
(signed)
83
[READ ONLY]
Temperature Setpoint – Zone 2
84
[READ ONLY]
Flow Temperature Setpoint –
Zone 1 (signed)
85
[READ ONLY]
Flow Temperature Setpoint –
Zone 1
86
[READ ONLY]
Flow Temperature Setpoint –
Zone 2 (signed)
87
[READ ONLY]
Flow Temperature Setpoint –
Zone 2
88
[READ ONLY]
Legionella Temperature Setpoint
(signed)
89
[READ ONLY]
Legionella Temperature Setpoint
90
[READ ONLY]
DHW Temperature Drop (signed)
91
[READ ONLY]
DHW Temperature Drop
92
[READ ONLY]
Modicon
Details
Address
0 = H/P
1 = IH
40081
2 = BH
3 = IH + BH
4 = Boiler
Temperature value in ºC multiplied by 100.
40082
(see note *)
Temperature value in ºC multiplied by 100.
40083
(see note **)
Temperature value in ºC multiplied by 100.
40084
(see note *)
Temperature value in ºC multiplied by 100.
40085
(see note **)
Temperature value in ºC multiplied by 100.
40086
(see note *)
Temperature value in ºC multiplied by 100.
40087
(see note **)
Temperature value in ºC multiplied by 100.
40088
(see note *)
Temperature value in ºC multiplied by 100.
40089
(see note **)
Temperature value in ºC multiplied by 100.
40090
(see note *)
Temperature value in ºC multiplied by 100.
40091
(see note **)
Temperature value in ºC multiplied by 10.
40092
0xFF38 = -20.0ºC ... 0x0433 = 107.5ºC
Temperature value in ºC multiplied by 10.
40093
0x0000 = 0ºC ... 0x0433 = 107.5ºC
0 = 0.0ºC ... 1075 = 107.5ºC