Input Register (Analogue Input)
Register Name
Addr
Temperature Setpoint – Zone 1
40
(signed)
Temperature Setpoint – Zone 1
41
Temperature Setpoint – Zone 2
42
(signed)
Temperature Setpoint – Zone 2
43
Flow Temperature Setpoint –
44
Zone 1 (signed)
Flow Temperature Setpoint –
45
Zone 1
Flow Temperature Setpoint –
46
Zone 2 (signed)
Flow Temperature Setpoint –
47
Zone 2
Legionella Temperature Setpoint
48
(signed)
Legionella Temperature Setpoint
49
DHW Temperature Drop (signed)
50
DHW Temperature Drop
51
Room Temperature – Zone 1
52
(signed)
Room Temperature – Zone 1
53
Modicon
Details
Address
Temperature value in ºC multiplied by 100.
30041
(see note *)
Temperature value in ºC multiplied by 100.
30042
(see note **)
Temperature value in ºC multiplied by 100.
30043
(see note *)
Temperature value in ºC multiplied by 100.
30044
(see note **)
Temperature value in ºC multiplied by 100.
30045
(see note *)
Temperature value in ºC multiplied by 100.
30046
(see note **)
Temperature value in ºC multiplied by 100.
30047
(see note *)
Temperature value in ºC multiplied by 100.
30048
(see note **)
Temperature value in ºC multiplied by 100.
30049
(see note *)
Temperature value in ºC multiplied by 100.
30050
(see note **)
Temperature value in ºC multiplied by 10.
30051
0xFF38 = -20.0ºC ... 0x0433 = 107.5ºC
Temperature value in ºC multiplied by 10.
30052
0x0000 = 0ºC ... 0x0433 = 107.5ºC
0 = 0.0ºC ... 1075 = 107.5ºC
Temperature value in ºC multiplied by 100.
30053
(see note *)
Temperature value in ºC multiplied by 100.
30054
(see note **)
Applicable Unit Type
57