Holding Register (Analogue Output)
Register Name
Addr
Model Profile 1
270
[READ ONLY]
Model Profile 2 (refrigerant
address)
271
[READ ONLY]
Energy Consumption Measured
Date – Year
279
[READ ONLY]
Energy Consumption Measured
Date – Month
280
[READ ONLY]
Energy Consumption Measured
Date – Day
281
[READ ONLY]
Last Measured Heating Energy
Consumption – kWh part
282
[READ ONLY]
Last Measured Heating Energy
Consumption – Wh part
283
[READ ONLY]
Last Measured Cooling Energy
Consumption – kWh part
284
[READ ONLY]
Last Measured Cooling Energy
Consumption – Wh part
285
[READ ONLY]
Last Measured DHW Energy
Consumption – kWh part
286
[READ ONLY]
Modicon
Details
Address
0 = FTC2B
1 = FTC4
2 = FTC5
128 = CAHV1A
129 = CAHV1B
130 = CRHV1A
40271
131 = CRHV1B
132 = EAHV1A
133 = EAHV1B
134 = QAHV1A
135 = QAHV1B
144 = PWFY1
0 = Address 0
...
40272
255 = Address 255
(addresses 7 – 255 not used for FTC)
Date of last energy consumption measurement –
40280
Year
Date of last energy consumption measurement –
40281
Month
Date of last energy consumption measurement –
40282
Day
Last measured heating energy consumption – kWh
40283
part of the value.
0 = 0kWh ... 65535 = 65535kWh
Last measured heating energy consumption – Wh
40284
part of the value.
0 = 0Wh ... 99 = 99Wh
Last measured cooling energy consumption – kWh
40285
part of the value.
0 = 0kWh ... 65535 = 65535kWh
Last measured cooling energy consumption – Wh
40286
part of the value.
0 = 0Wh ... 99 = 99Wh
Last measured DHW energy consumption – kWh
40287
part of the value.
0 = 0kWh ... 65535 = 65535kWh