Procon A1M Installation Manual page 81

Hide thumbs Also See for A1M:
Table of Contents

Advertisement

Holding Register (Analogue Output)
Register Name
Addr
Minimum Cooling Setpoint
326
[READ ONLY]
Maximum Cooling Setpoint
327
[READ ONLY]
Minimum Heating Setpoint
328
[READ ONLY]
Maximum Heating Setpoint
329
[READ ONLY]
Minimum Auto Setpoint
330
[READ ONLY]
Maximum Auto Setpoint
331
[READ ONLY]
Energy Consumption Data
Available
332
[READ ONLY]
Number of Fan Speeds
333
[READ ONLY]
Bypass Damper Available
334
[READ ONLY]
Modicon
Details
Address
Temperature value in ºC multiplied by 10.
0 = 0ºC ... 400 = 40ºC
40327
Note: Only available when 'Set Temperature on
Temperature Control Unit' value = 1 or 2.
Temperature value in ºC multiplied by 10.
0 = 0ºC ... 400 = 40ºC
40328
Note: Only available when 'Set Temperature on
Temperature Control Unit' value = 1 or 2.
Temperature value in ºC multiplied by 10.
0 = 0ºC ... 400 = 40ºC
40329
Note: Only available when 'Set Temperature on
Temperature Control Unit' value = 1 or 2.
Temperature value in ºC multiplied by 10.
0 = 0ºC ... 400 = 40ºC
40330
Note: Only available when 'Set Temperature on
Temperature Control Unit' value = 1 or 2.
Temperature value in ºC multiplied by 10.
0 = 0ºC ... 400 = 40ºC
40331
Note: Only available when 'Set Temperature on
Temperature Control Unit' value = 1 or 2.
Temperature value in ºC multiplied by 10.
0 = 0ºC ... 400 = 40ºC
40332
Note: Only available when 'Set Temperature on
Temperature Control Unit' value = 1 or 2.
0 = Not available
40333
1 = Available
40334
Values 1 – 4 valid.
0 = Not available
40335
1 = Available
Applicable Unit Type
79

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melcobems mini

Table of Contents