Holding Register (Analogue Output)
Register Name
Addr
Flow SW1 (IN2)
121
[READ ONLY]
Flow SW2 (IN3)
122
[READ ONLY]
Flow SW3 (IN7)
123
[READ ONLY]
Demand (IN4)
124
[READ ONLY]
Outdoor Thermo (IN5)
125
[READ ONLY]
DIP Switch SW2
126
[READ ONLY]
Heat Pump Master ON/OFF
127
[READ ONLY]
Heat Pump Slave 1 ON/OFF
(address 2 for CAHV/CRHV)
128
[READ ONLY]
Heat Pump Slave 2 ON/OFF
(address 3 for CAHV/CRHV)
129
[READ ONLY]
Heat Pump Slave 3 ON/OFF
(address 4 for CAHV/CRHV)
130
[READ ONLY]
Heat Pump Slave 4 ON/OFF
(address 5 for CAHV/CRHV)
131
[READ ONLY]
Heat Pump Slave 5 ON/OFF
(address 6 for CAHV/CRHV)
132
[READ ONLY]
Heat Pump Slave 6 ON/OFF
(address 7 for CAHV/CRHV)
133
[READ ONLY]
Heat Pump Slave 7 ON/OFF
(address 8 for CAHV/CRHV)
134
[READ ONLY]
Modicon
Details
Address
40122
0 = OFF, 1 = ON
40123
0 = OFF, 1 = ON
40124
0 = OFF, 1 = ON
40125
0 = OFF, 1 = ON
40126
0 = OFF, 1 = ON
Bit 0 = Switch 2-1 (0 = OFF, 1 = ON)
40127
...
Bit 9 = Switch 2-10 (0 = OFF, 1 = ON)
40128
0 = Stop, 1 = Run
40129
0 = Stop, 1 = Run
40130
0 = Stop, 1 = Run
40131
0 = Stop, 1 = Run
40132
0 = Stop, 1 = Run
40133
0 = Stop, 1 = Run
40134
0 = Stop, 1 = Run
40135
0 = Stop, 1 = Run
Applicable Unit Type