Input Register (Analogue Input)
Register Name
Addr
Water Pump 1 – PWM Duty
141
Water Pump 1 – PWM Duty
142
Feedback
3-Way Valve 1
143
H/C Control Type
144
MRC Prohibit
145
Version of Protocol (upper)
146
Version of Protocol (lower)
147
Version of Model (upper)
148
Version of Model (lower)
149
Capacity of Supplying Electricity
150
Modicon
Details
Address
Duty value in %
30142
0 = 0% ... 100 = 100%
Duty value in %
30143
0 = 0% ... 100 = 100%
0 = OFF (stop)
30144
1 = ON (run)
0 = Heating
30145
1 = Cooling
Bit packed value:
Bit 0 – System On/Off (0 = ON, 1 = Prohibit)
Bit 1 – Running Mode (0 = ON, 1 = Prohibit)
Bit 2 – Setting Temp (0 = ON, 1 = Prohibit)
30146
Bit 3 – Undefined (always 0)
Bit 4 – Function Setting (0 = Normal, 1 = Function
Setting)
Bits 5, 6 and 7 – Undefined (always 0)
Version of Protocol is a value in BCD
30147
e.g. V3.01 = 3 (upper) and 1 (lower)
Version of Protocol is a value in BCD
30148
e.g. V3.01 = 3 (upper) and 1 (lower)
Version of Model is a value in BCD
30149
e.g. V2.00 = 2 (upper) and 0 (lower)
Version of Model is a value in BCD
30150
e.g. V2.00 = 2 (upper) and 0 (lower)
Value in Watts
0 = 0,0 W
30151
...
255 = 25,5 W
Applicable Unit Type
65