Input Register (Analogue Input)
Register Name
Addr
Maximum Cooling Setpoint
186
Minimum Heating Setpoint
187
Maximum Heating Setpoint
188
Minimum Auto Setpoint
189
Maximum Auto Setpoint
190
Number of Fan Speeds
191
Set Temperature on
192
Temperature Control Unit
Modicon
Details
Address
Temperature value in ºC multiplied by 10.
0 = 0ºC ... 400 = 40ºC
30187
Note: Only available when 'Set Temperature on
Temperature Control Unit' value = 1 or 2.
Temperature value in ºC multiplied by 10.
0 = 0ºC ... 400 = 40ºC
30188
Note: Only available when 'Set Temperature on
Temperature Control Unit' value = 1 or 2.
Temperature value in ºC multiplied by 10.
0 = 0ºC ... 400 = 40ºC
30189
Note: Only available when 'Set Temperature on
Temperature Control Unit' value = 1 or 2.
Temperature value in ºC multiplied by 10.
0 = 0ºC ... 400 = 40ºC
30190
Note: Only available when 'Set Temperature on
Temperature Control Unit' value = 1 or 2.
Temperature value in ºC multiplied by 10.
0 = 0ºC ... 400 = 40ºC
30191
Note: Only available when 'Set Temperature on
Temperature Control Unit' value = 1 or 2.
30192
Values 1 – 4 valid.
0 = No set temperature display
30193
1 = RA (Return Air) temperature
2 = SA (Supply Air) temperature
Applicable Unit Type
84