Procon A1M Installation Manual page 52

Hide thumbs Also See for A1M:
Table of Contents

Advertisement

Holding Register (Analogue Output)
Register Name
Addr
Water Outlet Temperature 2
(signed)
258
[READ ONLY]
Water Outlet Temperature 2
259
[READ ONLY]
Evaporating Temperature 2
(signed)
260
[READ ONLY]
Evaporating Temperature 2
261
[READ ONLY]
Water Pump 1 – PWM Duty
262
[READ ONLY]
Water Pump 1 – PWM Duty
Feedback
263
[READ ONLY]
3-Way Valve 1
264
[READ ONLY]
Version of Protocol (upper)
265
[READ ONLY]
Version of Protocol (lower)
266
[READ ONLY]
Version of Model (upper)
267
[READ ONLY]
Version of Model (lower)
268
[READ ONLY]
Capacity of Supplying Electricity
269
[READ ONLY]
Modicon
Details
Address
Temperature value in ºC multiplied by 100.
40259
(see note *)
Temperature value in ºC multiplied by 100.
40260
(see note **)
Temperature value in ºC multiplied by 100.
40261
(see note *)
Temperature value in ºC multiplied by 100.
40262
(see note **)
Duty value in %
40263
0 = 0% ... 100 = 100%
Duty value in %
40264
0 = 0% ... 100 = 100%
0 = OFF (stop)
40265
1 = ON (run)
Version of Protocol is a value in BCD
40266
e.g. V3.01 = 3 (upper) and 1 (lower)
Version of Protocol is a value in BCD
40267
e.g. V3.01 = 3 (upper) and 1 (lower)
Version of Model is a value in BCD
40268
e.g. V2.00 = 2 (upper) and 0 (lower)
Version of Model is a value in BCD
40269
e.g. V2.00 = 2 (upper) and 0 (lower)
Value in Watts
0 = 0,0 W
40270
...
255 = 25,5 W
Applicable Unit Type
50

Hide quick links: