Omron CS1W-CT041 Operation Manual page 160

High-speed counter units
Hide thumbs Also See for CS1W-CT041:
Table of Contents

Advertisement

F"")"-$).#+
Error Code 1
Error Code 2
0330
Counter
No.
0331
Counter
No.
0335
Offset (BCD)
Clearing DM-configuration
errors
Error
Range
Invalid
No.
Range Limit(s) /
(BCD)
Comparison
/
Value
CV No.
(BCD)
CV No.
Comparison
(BCD)
Values are equal
Rate Ranges
overlap
DM-configuration errors can be cleared by correcting the faulty settings in Data
Memory and consecutively transferring the new configuration data again to the
Unit. To transfer the configuration data you can choose from one out of two possi-
bilities:
Turn the power of the CS1-system ON.
Restart the High-speed Counter Unit (refer to 4-1-2 "Special I/O Units Restart
bits").
Description
If the Unit is in Range Mode: Lower and/or Upper
Range Limit is/are outside Counting Range.
Counter No. indicates the Counter number and
Range No. indicates the Range number.
If the Unit is in Comparison Mode: Comparison
value is outside Counting Range. Counter No.
indicates the Counter number and CV No.
indicates the Comparison Value number.
(The counting range of Circular and Linear
Counters can be specified, refer to 3-2-2 "Circular
Counter" and 3-2-3 "Linear Counter" for more
information).
For the Counter, with the Counter Number as
reported in Error Code 2, one or more Comparison
Values are equal. CV No. indicates the
Comparison Value number.
The Rate Ranges located at D20000 + (Nx100) +
Offset overlap (N=Machine Number)